NOTICE
•
Reduce common mode interferences by
establishing a low impedance current path to
the frequency converter.
•
To ensure optimum EMC performance, use a
De-Coupling plate kit (ordering numbers
132B0106 or 132B0107)
For voltage rating, wire size and fuse selection, see the
VLT
®
Micro Drive Quick Guide
.
4.1.18 Dimensions
100
+10
0
300
+20
0
M6
1
W
PE
d
LO
A
D
LINE
5.5
h1
l1
h2
7.8
W1
W2
l2
h
l2
h3
Ø11
Ø5.5
M4(3x)
130BC163.10
Frame
M1
M2
M3
w [mm]
70
75
90
d [mm]
55
65
69
h [mm]
190
210
300
h3 [mm]
230
250
340
w1 [mm]
40
40
55.6
h1 [mm]
213
233
323
w2 [mm]
55
59
69
h2 [mm]
140
166.5
226
l1 [mm]
45
38.5
68
l2 [mm]
7.6
8
9.3
PE (metric)
M6
M6
M6
Weight [kg]
2
3
5
Table 4.7 Dimension Data
Illustration 4.33 Dimensions
Selection
VLT
®
Micro Drive FC 51 Design Guide
36
MG02K302 - Rev. 2013-12-03
4