1.
2.
3.
4.
5.
6.
7.
4.7.1 Performing Functional Tests
Procedure
Remove 24 V DC voltage supply at terminal 37.
Check if the LCP shows
Alarm 68, Safe Stop
or
Warning 68, Safe Stop
.
Verify that the drive trips the unit.
Verify that the motor is coasting and comes to a complete stop.
Verify that the motor cannot be started.
Reconnect 24 V DC supply to terminal 37.
Verify that the motor is not started automatically and restarts only by giving a reset signal via bus, digital I/O, or [Reset] key.
AQ313340186453en-00101 / 130R0544 | 15
Danfoss A/S © 2021.03
Commissioning
Safe Torque Off
Operating Guide