background image

3.


Connection and application examples are found in the chapter 

Application Examples

.

Complete wiring according to the instructions given in the Operating Guide of the drive.

3.3 Installation in Combination with VLT® PTC Thermistor Card MCB 112

N O T I C E

The combination of VLT® PTC Thermistor Card MCB 112 and STO function is only available for VLT® HVAC Drive FC 102, VLT®
Refrigeration Drive FC 103, VLT® AQUA Drive FC 202, VLT® AutomationDrive FC 302, and VLT® AutomationDrive FC 301 enclosure
size A1.

VLT® PTC Thermistor Card MCB 112 uses terminal 37 as its safety-related switch-off channel.

Ensure that the output X44/12 of MCB 112 is AND-ed with the safety-related sensor (for example, emergency stop button and
safeguard switch) that activates STO. This means that the output to STO terminal 37 is high (24 V) only if both the signal from
MCB 112 output X44/12 and the signal from the safety-related sensor are high. If at least 1 of the 2 signals is low, the output to
terminal 37 must be low too.
Ensure that the safety device with AND-logic complies with the needed safety level.
Short-circuit protect the connection from the output of the safety device with safe AND-logic to the STO terminal 37.

e

3

0

b

a

9

6

7

.1

3

Digital input

PTC
sensor

Non-hazardous area

Hazardous
area

X44/

PTC Thermistor Card

MCB 112

1 2 3 4 5 6 7 8 9 10 1112

Safety device

Manual restart

SIL 2

Safe AND input

Safe output

S

a

fe

 i

n

p

u

t

DI

DI

      STO
  

Par. 5-19

Terminal 37 Safe Stop

12 13 18 19 27 29 32 33 20 37

e.g. Par 5-15

Illustration 3: Combination of an STO Application and an MCB 112 Application

The illustration shows a restart input for the external safety device. This means that in this installation, 

parameter 5-19 Terminal 37

Safe Stop

 can be set to value 

[7] PTC 1 & Relay W

 or 

[8] PTC 1 & Relay A/W

. Refer to VLT® PTC Thermistor Card MCB 112 Operating

Guide for further details.

AQ313340186453en-00101 / 130R0544

12 | Danfoss A/S © 2021.03

Installation

Safe Torque Off

Operating Guide

Содержание VLT FC Series

Страница 1: ...Operating Guide Safe Torque Off VLT Frequency Converters vlt drives danfoss com...

Страница 2: ......

Страница 3: ...Card MCB 112 12 Commissioning 13 Safety Instructions 10 Activating STO 13 Parameter Settings for STO Used With VLT PTC Thermistor Card MCB 112 13 Automatic Manual Restart Behavior 13 STO Commissionin...

Страница 4: ...tices Regarding Technical Data 21 European Directives 21 Safety Standards 21 Safety Function 21 Safety Performance 21 Appendix 22 Abbreviations 22 Conventions 22 AQ313340186453en 00101 130R0544 4 Danf...

Страница 5: ...of operational safety Before integrating and using STO in an installation carry out a thorough risk analysis on the installation to determine whether the STO functionality and safety levels are appro...

Страница 6: ...lel Drive Modules T or U at digit 18 of the type code 1 4 Applied Standards and Compliance Using the STO on terminal 37 requires that the user fulfills all provisions for safety including relevant law...

Страница 7: ...en in the operating guide of the drive Have good knowledge of the generic and specialist standards applicable to the specific application 2 3 Responsibilities of Users of Safety related Power Drive Sy...

Страница 8: ...by coasting If this limitation is not acceptable for example because it causes danger use the appropriate stopping mode to stop the drive and machinery before using the STO function Depending on the...

Страница 9: ...to the machine actuators to achieve the stop Power is removed from the actuators when the stop is achieved according to EN 61800 5 2 Safe Stop 1 SS1 Stop Category 2 is a controlled stop with power ava...

Страница 10: ...er grounding and compliance with all applicable national and local safe ty regulations See 2 5 Safety Precautions and the Operating Guide of the relevant drive Also always observe the instructions pro...

Страница 11: ...w jumper wire between control terminals 37 and 12 or 13 Cutting or breaking the yellow jumper is not sufficient to avoid short circuiting see jumper in Illustration 1 12 13 37 e30ba874 11 Illustration...

Страница 12: ...al from the safety related sensor are high If at least 1 of the 2 signals is low the output to terminal 37 must be low too Ensure that the safety device with AND logic complies with the needed safety...

Страница 13: ...ing are selected and MCB 112 is triggered the drive issues alarm 72 Dangerous Failure and coasts the motor safely without automatic restart Do not select 4 PTC 1 Alarm and 5 PTC 1 Warning when an exte...

Страница 14: ...nsure that the motor remains in the coasted state and that the mechanical brake if connected remains activated Send a reset signal via bus digital I O or Reset key Ensure that the motor is operational...

Страница 15: ...ve trips the unit Verify that the motor is coasting and comes to a complete stop Verify that the motor cannot be started Reconnect 24 V DC supply to terminal 37 Verify that the motor is not started au...

Страница 16: ...1 PL c ISO 13849 1 or SIL1 EN 62061 and IEC 61508 The STO function is activated via 1 NC positively operated switch contact according to IEC 60947 1 IEC 60947 5 1 and IEC 60947 5 5 The PL c the comple...

Страница 17: ...The device used for activation of STO and safety relay must be suitable for the selected category PL and SIL When implementing the emergency stop pay attention to the following tips Any non safety rel...

Страница 18: ...op or emergency stop command the drive is halted Where the safety control system must be in accordance with PL e ISO 13849 1 or SIL3 EN 62061 and IEC 61508 it requires a 2 channel stop for the STO fun...

Страница 19: ...ty relay MSR 33 CH channel 1 BL FC 300 safe stop terminal 37 CH channel 2 BL output contactor 100S C Illustration 9 Safety related Block Diagram 5 5 Emergency Stop of Multiple Drives Category 3 PL d S...

Страница 20: ...omponents The application designer is responsible for selecting suitable components The cable shown as bold in Illustration 10 has to be short circuit protected according to ISO 13849 2 table D 4 To f...

Страница 21: ...62061 Safety integrity level SIL2 SIL CL2 Probability of dangerous failure per hour PFH 1E 10 h 1E 8 h for specific variants High Demand Mode 1 2 Probability of dangerous failure on demand PFD 1E 10...

Страница 22: ...EC 61508 Average probability of failure on demand value used for low demand operation PL EN ISO 13849 1 Discrete level used to specify the ability of safety related parts of control systems to perform...

Страница 23: ...rms warnings All dimensions in drawings are in metric values imperial values in brackets An asterisk indicates the default setting of a parameter AQ313340186453en 00101 130R0544 23 Danfoss A S 2021 03...

Страница 24: ...8 9 9 EN ISO 13849 1 5 EN 62061 5 16 17 18 IEC EN 61508 6 IEC EN 61800 5 2 6 IEC EN 62601 6 ISO 13849 1 6 16 17 18 21 21 21 22 IEC EN 60204 1 6 IEC 60529 7 ISO 13849 2 7 16 17 18 19 ISO 12100 8 13 EN...

Страница 25: ...AQ313340186453en 00101 130R0544 25 Danfoss A S 2021 03 Index Safe Torque Off Operating Guide...

Страница 26: ...rinted material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes...

Отзывы: