3.8. Final Set-Up and Test
3.8.1. Final Set-Up and Test
To test the set-up and ensure that the adjustable frequency drive is running, follow these steps.
Step 1. Locate the motor nameplate
NOTE
The motor is either star- (Y) or delta-connected (
Δ
). This information is located on
the motor nameplate data.
Step 2. Enter the motor nameplate data
in this parameter list.
To access this list, first press the [QUICK
MENU] key, then select “Q2 Quick Set-up”.
1. Motor Power [kW]
or Motor Power [HP]
par. 1-20
par. 1-21
2. Motor Voltage
par. 1-22
3. Motor Frequency
par. 1-23
4. Motor Current
par. 1-24
5. Motor Nominal Speed
par. 1-25
Step 3. Activate the Automatic Motor
Adaptation (AMA)
Performing an AMA will ensure optimum performance. The AMA measures the values
from the motor model equivalent diagram.
1.
Connect terminal 37 to terminal 12 (if terminal 37 is available).
2.
Connect terminal 27 to terminal 12, or set par. 5-12 to 'No function' (par. 5-12 [0])
3.
Activate the AMA par. 1-29.
3. How to Install
VLT
®
Automation Drive FC 300
Instruction Manual High Power
70
MG.33.U1.22 - VLT
®
is a registered Danfoss trademark.
3