1536 An exception in the Application
Orientated Control is registered.
Debug information written in LCP
1792 DSP watchdog is active. Debug-
ging of power part data Motor Ori-
entated Control not transferred
correctly
2049 Power data restarted
2315 Missing SW version from power
unit
2816 Stack overflow Control board
module
2817 Scheduler slow tasks
2818 Fast tasks
2819 Parameter thread
2820 LCP stack overflow
2821 Serial port overflow
2822 USB port overflow
3072-
5122
Parameter value is outside its lim-
its. Perform an initialization. Pa-
rameter number causing the
alarm: Subtract the code from
3072. Ex Error code 3238:
3238-3072 = 166 is outside the
limit
5123 Option in slot A: Hardware incom-
patible with Control board hard-
ware
5124 Option in slot B: Hardware incom-
patible with Control board hard-
ware
5125 Option in slot C0: Hardware in-
compatible with Control board
hardware
5126 Option in slot C1: Hardware in-
compatible with Control board
hardware
5376-
6231
Out of memory
WARNING 40, Overload of Digital Out-
put Terminal 27:
Check the load connected to terminal 27 or
remove short-circuit connection. Check pa-
rameters 5-00 and 5-01.
WARNING 41, Overload of Digital Out-
put Terminal 29:
Check the load connected to terminal 29 or
remove short-circuit connection. Check pa-
rameters 5-00 and 5-02.
WARNING 42, Overload of Digital Out-
put On X30/6:
Check the load connected to X30/6 or remove
short-circuit connection. Check parameter
5-32.
WARNING 42, Overload of Digital Out-
put On X30/7:
Check the load connected to X30/7 or remove
short-circuit connection. Check parameter
5-33.
WARNING 47, 24 V supply low:
The external 24 V DC backup power supply
may be overloaded; otherwise, contact your
Danfoss supplier.
WARNING 48, 1.8 V supply low:
Contact your Danfoss supplier.
WARNING 49, Speed limit:
The speed is not within the range specified in
par. 4-11 and par. 4-13.
ALARM 50, AMA calibration failed:
Contact your Danfoss supplier.
ALARM 51, AMA check Unom and Inom:
The setting of motor voltage, motor current
and motor power is presumably wrong. Check
the settings.
ALARM 52, AMA low Inom:
The motor current is too low. Check the set-
tings.
ALARM 53, AMA motor too big:
The motor is too big for the AMA to be carried
out.
ALARM 54, AMA motor too small:
The motor is too big for the AMA to be carried
out.
ALARM 55, AMA par. out of range:
The par. values found from the motor are out-
side the acceptable range.
ALARM 56, AMA interrupted by user:
The AMA has been interrupted by the user.
ALARM 57, AMA timeout:
Try to start the AMA again a number of times
until it is carried out. Please note that repea-
ted runs may heat the motor to a level where
the resistances Rs and Rr are increased. In
most cases, however, this is not critical.
ALARM 58, AMA internal fault:
Contact your Danfoss supplier.
6. Warnings and Alarms
VLT
®
Automation Drive FC 300
Instruction Manual High Power
134
MG.33.U1.22 - VLT
®
is a registered Danfoss trademark.
6