1-14 Damping Gain
Range:
Function:
of the PM machine. High damping gain
will give high dynamic performance and
low damping gain will give low dynamic
performance. The dynamic performance is
related to the machine data and load type.
If the damping gain is too high or low the
control will become unstable.
120%
*
[0-250%]
1-15 Low Speed Filter Time Const.
Range:
Function:
Size related
*
[0.01 - 20 s] High pass-filter damping time
constant determines the response
time to load steps. Obtain quick
control through a short damping
time constant. However, if this value
is too short, the control gets
unstable. This time constant is used
below 10% rated speed.
Size related
*
[0.01 - 20.00
s]
1-16 High Speed Filter Time Const.
Range:
Function:
Size related
*
[0.01 - 20 s]
High pass-filter damping time
constant determines the response
time to load steps. Obtain quick
control through a short damping
time constant. However, if this
value is too short, the control gets
unstable. This time constant is used
above 10% rated speed.
Size related
*
[0.01-20.00 s]
1-17 Voltage filter time const.
Range:
Function:
Size
related
*
[0.001 - 1 s]
Machine Supply Voltage Filter
Time constant is used for reducing
the influence of high frequency
ripples and system resonances in
the calculation of machine supply
voltage. Without this filter, the
ripples in the currents can distort
the calculated voltage and affects
the stability of the system.
Size
related
*
[0.001-1.000 s]
3.3.4 1-2* Motor Data
Parameter group 1-2* comprises input data from the
nameplate on the connected motor.
NOTE
Changing the value of these parameters affects the setting
of other parameters.
NOTE
,
,
and
will not have effect
when
= [1] PM, non salient SPM.
1-20 Motor Power [kW]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00
kW]
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
Depending on the choices made in
, either
or
is
made invisible.
NOTE
This parameter cannot be adjusted
while the motor is running.
1-21 Motor Power [HP]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00 hp]
Enter the nominal motor power in HP
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
Depending on the choices made in
, either
or
is
made invisible.
NOTE
This parameter cannot be adjusted
while the motor is running.
1-22 Motor Voltage
Range:
Function:
Size
related
*
[ 10 -
1000 V]
Enter the nominal motor voltage
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
NOTE
This parameter cannot be adjusted
while the motor is running.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
37
3