3.6 Additional Inputs and Outputs
3.6.1 Wiring Schematic
When wired and properly programmed, the control terminals provide:
•
Feedback, reference, and other input signals to the frequency converter.
•
Output status and fault conditions from the frequency converter.
•
Relays to operate auxiliary equipment.
•
A serial communication interface.
•
24 V common.
Control terminals are programmable for various functions by selecting parameter options through the local control panel
(LCP) on the front of the unit or through external sources. Most control wiring is customer-supplied, unless specified in the
factory order.
*
91 (L1)
92 (L2)
93 (L3)
PE
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4–20 mA
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
20 (COM D IN)
15 mA
200 mA
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
0/4–20 mA
03
0–10 V DC
+10 V DC
0-10 V DC
0/4–20 mA
240 V AC, 2 A
24 V DC
02
01
05
04
06
240 V AC, 2 A
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
19 (D IN)
24 V (NPN)
0 V (PNP)
27
24 V
0 V
(D IN/OUT)
0 V (PNP)
24 V (NPN)
(D IN/OUT)
0 V
24 V
29
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
1
2
ON
S201
ON
2
1S202
ON=0–20 mA
OFF=0–10 V
95
400 V AC, 2 A
P 5-00
(R+) 82
(R-) 81
37 (D IN)
+
-
+
-
130BA544.13
(P RS485) 68
(N RS485) 69
(COM RS485) 61
0V
5 V
S801
RS485
RS485
2
1
ON
S801
3-phase
power
input
DC bus
Switch mode
power supply
Motor
Analog output
Interface
Relay1
Relay2
ON=Terminated
OFF=Open
Brake
resistor
(NPN) = Sink
(PNP) = Source
Illustration 3.24 Basic Wiring Schematic
A=Analog, D=Digital
*Terminal 37 (optional) is used for STO. For STO installation instructions, refer to the
VLT
®
Frequency Converters - Safe Torque
Off Operating Instructions
.
**Do not connect cable screen.
System Integration
Design Guide
MG16G202