380–480 V AC
FC 102
N110
N132
N160
N200
N250
N315
FC 103
N110
N132
N160
N200
N250
N315
FC 202
N110
N132
N160
N200
N250
N315
380–500 V AC
FC 302
N90k
N110
N132
N160
N200
N250
Overcurrent Warning
[A
rms
]
327
392
481
583
731
888
Overcurrent Alarm
1
(1.5 s delay)
[A
rms
]
330
395
483
585
734
893
Ground Fault Alarm
[A
rms
]
27
32
39
47
59
72
Short Circuit Alarm
[Apk]
593
711
868
1051
1318
1595
Heatsink Overtemperature
°
F [°C]
230 [110]
230 [110]
230 [110]
230 [110]
230 [110]
230 [110]
Heatsink Undertemperature
Warning
°
F [°C]
32 [0]
32 [0]
32 [0]
32 [0]
32 [0]
32 [0]
Control Card Overtemperature
°
F [°C]
167 [75]
167 [75]
167 [75]
176 [80]
176 [80]
176 [80]
Line Phase Warning (30 s delay)
DC Bus Ripple Vpkpk
80
80
80
80
80
80
Line Phase Alarm (60 s delay)
DC Bus Ripple Vpkpk
80
80
80
80
80
80
1) Based on crest factor of 1.414
Table 1.17 Warning and Alarm Trip Points
525–690 V AC
FC 102
N75
N90
N110
N132
N160
N200
N250
N315
N400
FC 103
N75
N90
N110
N132
N160
N200
N250
N315
N400
FC 202
N75
N90
N110
N132
N160
N200
N250
N315
N400
FC 302
N55
N75
N90
N110
N132
N160
N200
N250
N315
Overcurrent Warning
[A
rms
]
141
167
209
253
300
372
468
561
666
Overcurrent Alarm
1
(1.5 s delay)
[A
rms
]
255
255
255
255
330
483
483
585
734
Ground Fault Alarm
[A
rms
]
11
14
17
21
24
30
38
45
54
Short Circuit Alarm
[Apk]
459
459
459
459
593
870
869
1050
1319
Heatsink Overtemperature
°
F [°C]
230
[110]
230
[110]
230
[110]
230
[110]
230
[110]
230
[110]
230
[110]
230
[110]
230
[110]
Heatsink Undertem-
perature Warning
°
F [°C]
32 [0]
32 [0]
32 [0]
32 [0]
32 [0]
32 [0]
32 [0]
32 [0]
32 [0]
Control Card Overtem-
perature
°
F [°C]
167 [75] 167 [75] 167 [75] 167 [75] 167 [75] 167 [75] 176 [80] 176 [80] 176 [80]
Line Phase Warning
(30 s delay)
DC Bus Ripple
Vpkpk
80
80
80
80
80
80
80
80
80
Line Phase Alarm
(60 s delay)
DC Bus Ripple
Vpkpk
80
80
80
80
80
80
80
80
80
1) Based on crest factor of 1.414
Table 1.18 Warning and Alarm Trip Points