9 Specifications
9.1 Electrical Data
9.1.1 Mains Supply 3x380–480 V AC
N355
N400
N450
Normal overload
NO
NO
NO
(Normal overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
355
400
450
Typical shaft output at 460 V [hp]
500
600
600
Typical shaft output at 480 V [kW]
400
500
530
Enclosure size
E1h/E3h
E1h/E3h
E1h/E3h
Output current (3-phase)
Continuous (at 400 V) [A]
658
745
800
Intermittent (60 s overload)
(at 400 V) [A]
724
820
880
Continuous (at 460/480 V) [A]
590
678
730
Intermittent (60 s overload)
(at 460/480 V) [A]
649
746
803
Continuous kVA (at 400 V) [kVA]
456
516
554
Continuous kVA (at 460 V) [kVA]
470
540
582
Continuous kVA (at 480 V) [kVA]
511
587
632
Maximum input current
Continuous (at 400 V) [A]
634
718
771
Continuous (at 460/480 V) [A]
569
653
704
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
2
(AWG)]
1)
5x240 (5x500 mcm)
5x240 (5x500 mcm)
5x240 (5x500 mcm)
- Mains and motor with brake [mm
2
(AWG)]
1)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
- Brake or regeneration [mm
2
(AWG)]
1)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Maximum number and size of cables per phase (E3h)
- Mains and motor [mm
2
(AWG)]
1)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Brake [mm
2
(AWG)]
1)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
- Load share or regeneration [mm
2
(AWG)]
1)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
Maximum external mains fuses [A]
2)
800
800
800
Estimated power loss at 400 V [W]
3), 4
6928
8036
8783
Estimated power loss at 460 V [W]
3), 4
5910
6933
7969
Efficiency
4)
0.98
0.98
0.98
Output frequency
0–590 Hz
0–590 Hz
0–590 Hz
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [
°
C (
°
F)]
80 (176)
80 (176)
80 (176)
Power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
Fan power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
Active in-rush card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
Table 9.1 Technical Specifications, Mains Supply 3x380–480 V AC
Specifications
Operating Guide
MG16P222
Danfoss A/S © 04/2018 All rights reserved.
79
9
9
Содержание VLT FC 103
Страница 2: ......
Страница 119: ...Index Operating Guide MG16P222 Danfoss A S 04 2018 All rights reserved 117...