Trip lock
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, cycle
power to the drive. Reset the drive manually
by 1 of the following:
•
Pressing [Reset].
•
Remotely by control terminals.
•
Via serial communication.
Table 8.3 Operation Status
8.4 Warning and Alarm Types
The drive software issues warnings and alarms to assist in
diagnosing issues. The warning or alarm number appears
in the LCP.
Warning
A warning indicates the drive has encountered an
abnormal operating condition that leads to an alarm. A
warning stops when the abnormal condition is removed or
resolved.
Alarm
An alarm indicates a fault that requires immediate
attention. The fault always triggers a trip or trip lock. Reset
the drive after an alarm.
Reset the drive in any of 4 ways:
•
Press [Reset]/[Off/Reset].
•
Digital reset input command.
•
Serial communication reset input command.
•
Auto reset.
Trip
When tripping, the drive suspends operation to prevent
damage to the drive and other equipment. When a trip
occurs, the motor coasts to a stop. The drive logic
continues to operate and monitor the drive status. After
the fault condition is remedied, the drive is ready for a
reset.
Trip lock
When trip locking, the drive suspends operation to prevent
damage to the drive and other equipment. When a trip
lock occurs, the motor coasts to a stop. The drive logic
continues to operate and monitor the drive status. The
drive starts a trip lock only when serious faults occur that
can damage the drive or other equipment. After the faults
are fixed, cycle the input power before resetting the drive.
Warning and alarm displays
•
A warning is shown in the LCP along with the
warning number.
•
An alarm flashes along with the alarm number.
130BP086.12
Status
0.0Hz 0.000kW 0.00A
0.0Hz
0
Earth Fault [A14]
Auto Remote Trip
1(1)
Illustration 8.3 Alarm Example
In addition to the text and alarm code in the LCP, there are
3 status indicator lights.
Back
Can
cel
In
fo
OK
On
Alarm
Warn.
130BB467.11
Warning indicator light
Alarm indicator light
Warning
On
Off
Alarm
Off
On (flashing)
Trip lock
On
On (flashing)
Illustration 8.4 Status Indicator Lights
8.5 List of Warnings and Alarms
The following warning and alarm information defines each
warning or alarm condition, provides the probable cause
for the condition, and details a remedy or troubleshooting
procedure.
WARNING 1, 10 Volts low
The control card voltage is less than 10 V from terminal 50.
Remove some of the load from terminal 50, as the 10 V
supply is overloaded. Maximum 15 mA or minimum 590
Ω
.
A short circuit in a connected potentiometer or incorrect
wiring of the potentiometer can cause this condition.
Troubleshooting
•
Remove the wiring from terminal 50. If the
warning clears, the problem is with the wiring. If
the warning does not clear, replace the control
card.
Maintenance, Diagnostics, a...
VLT® Refrigeration Drive FC 103
66
Danfoss A/S © 04/2018 All rights reserved.
MG16P222
8
8
Содержание VLT FC 103
Страница 2: ......
Страница 119: ...Index Operating Guide MG16P222 Danfoss A S 04 2018 All rights reserved 117...