ALARM 16, Short circuit
There is short-circuiting in the motor or motor wiring.
Troubleshooting
•
Remove the power to the drive and repair the
short circuit.
WARNING
HIGH VOLTAGE
Drives contain high voltage when connected to AC mains
input, DC supply, or load sharing. Failure to use qualified
personnel to install, start up, and maintain the drive can
result in death or serious injury.
•
Disconnect power before proceeding.
WARNING/ALARM 17, Control word timeout
There is no communication to the drive.
The warning is only active when
parameter 8-04 Control
Word Timeout Function
is NOT set to
[0] Off
.
If
parameter 8-04 Control Word Timeout Function
is set to
[5]
Stop and trip
, a warning appears, and the drive ramps
down to a stop and shows an alarm.
Troubleshooting
•
Check the connections on the serial communi-
cation cable.
•
Increase
parameter 8-03 Control Word Timeout
Time
.
•
Check the operation of the communication
equipment.
•
Verify that proper EMC installation was
performed.
WARNING/ALARM 20, Temp. input error
The temperature sensor is not connected.
WARNING/ALARM 21, Parameter error
The parameter is out of range. The parameter number is
shown in the display.
Troubleshooting
•
Set the affected parameter to a valid value.
WARNING 22, Hoist mechanical brake
0 = The torque reference was not reached before timeout.
1 = There was no brake feedback before the timeout.
WARNING 23, Internal fan fault
The fan warning function is a protective function that
checks if the fan is running/mounted. The fan warning can
be disabled in
parameter 14-53 Fan Monitor
(
[0] Disabled
).
There is a feedback sensor mounted in the fan. If the fan is
commanded to run and there is no feedback from the
sensor, this alarm appears. This alarm also shows if there is
a communication error between the fan power card and
the control card.
Check the alarm log (see
chapter 3.6 Local Control Panel
) for the report value associated with this warning.
If the report value is 2, there is a hardware problem with 1
of the fans. If the report value is 12, there is a communi-
cation problem between the fan power card and the
control card.
Fan troubleshooting
•
Cycle power to the drive and check that the fan
operates briefly at start-up.
•
Check for proper fan operation. Use
parameter
group 43-** Unit Readouts
to show the speed of
each fan.
Fan power card troubleshooting
•
Check the wiring between the fan power card
and the control card.
•
Fan power card may need to be replaced.
•
Control card may need to be replaced.
WARNING 24, External fan fault
The fan warning function is a protective function that
checks if the fan is running/mounted. The fan warning can
be disabled in
parameter 14-53 Fan Monitor
(
[0] Disabled
).
There is a feedback sensor mounted in the fan. If the fan is
commanded to run and there is no feedback from the
sensor, this alarm appears. This alarm also shows if there is
a communication error between the power card and the
control card.
Check the alarm log (see
chapter 3.6 Local Control Panel
) for the report value associated with this warning.
If the report value is 1, there is a hardware problem with 1
of the fans. If the report value is 11, there is a communi-
cation problem between the power card and the control
card.
Fan troubleshooting
•
Cycle power to the drive and check that the fan
operates briefly at start-up.
•
Check for proper fan operation. Use
parameter
group 43-** Unit Readouts
to show the speed of
each fan.
Power card troubleshooting
•
Check the wiring between the power card and
the control card.
•
Power card may need to be replaced.
•
Control card may need to be replaced.
WARNING 25, Brake resistor short circuit
The brake resistor is monitored during operation. If a short
circuit occurs, the brake function is disabled and the
warning appears. The drive is still operational, but without
the brake function.
Maintenance, Diagnostics, a...
Operating Guide
MG16P222
Danfoss A/S © 04/2018 All rights reserved.
69
8
8
Содержание VLT FC 103
Страница 2: ......
Страница 119: ...Index Operating Guide MG16P222 Danfoss A S 04 2018 All rights reserved 117...