Symptom
Possible cause
Test
Solution
Open power fuses or circuit
breaker trip
Phase to phase short.
Motor or panel has a short phase
to phase. Check motor and panel
phase for shorts.
Eliminate any shorts detected.
Motor overload.
Motor is overloaded for the
application.
Perform startup test and verify
motor current is within specifi-
cations. If motor current is
exceeding nameplate full load
current, motor may run only with
reduced load. Review the specifi-
cations for the application.
Loose connections.
Perform pre-startup check for loose
connections.
Tighten loose connections.
Line power current
imbalance greater than 3%
Problem with line power (See
Alarm 4 Mains phase loss
description).
Rotate input power leads into the
adjustable frequency drive one
position: A to B, B to C, C to A.
If imbalanced leg follows the wire,
it is a power problem. Check line
power supply.
Problem with the adjustable
frequency drive.
Rotate input power leads into the
adjustable frequency drive one
position: A to B, B to C, C to A.
If imbalance leg stays on same
input terminal, it is a problem with
the unit. Contact the supplier.
Motor current imbalance
greater than 3%
Problem with motor or motor
wiring.
Rotate output motor leads one
position: U to V, V to W, W to U.
If imbalanced leg follows the wire,
the problem is in the motor or
motor wiring. Check motor and
motor wiring.
Problem with the adjustable
frequency drives.
Rotate output motor leads one
position: U to V, V to W, W to U.
If imbalance leg stays on same
output terminal, it is a problem
with the unit. Contact the supplier.
Acoustic noise or vibration
(e.g., a fan blade is making
noise or vibrations at
certain frequencies)
Resonances, e.g., in the motor/fan
system.
Bypass critical frequencies by using
parameters in parameter group
4-6* Speed Bypass
.
Check if noise and/or vibration
have been reduced to an
acceptable limit.
Turn off overmodulation in
14-03 Overmodulation
.
Change switching pattern and
frequency in parameter group
14-0* Inverter Switching.
Increase Resonance Dampening in
1-64 Resonance Dampening
.
Table 9.1
Basic Troubleshooting
VLT
®
HVAC Drive D-Frame
Instruction Manual
MG16D222 - VLT
®
is a registered Danfoss trademark
9-3
9
9
Содержание VLT FC 100
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual 110 400 kW D Frame VLT HVAC Drive FC 100...
Страница 2: ......
Страница 4: ...Safety VLT HVAC Drive D Frame Instruction Manual MG16D222 VLT is a registered Danfoss trademark...
Страница 8: ...Contents VLT HVAC Drive D Frame Instruction Manual MG16D222 VLT is a registered Danfoss trademark...
Страница 14: ...Introduction VLT HVAC Drive D Frame Instruction Manual 1 6 MG16D222 VLT is a registered Danfoss trademark 1 1...
Страница 40: ...Installation VLT HVAC Drive D Frame Instruction Manual 2 26 MG16D222 VLT is a registered Danfoss trademark 2 2...
Страница 58: ...Programming VLT HVAC Drive D Frame Instruction Manual 5 10 MG16D222 VLT is a registered Danfoss trademark 5 5...
Страница 98: ...www danfoss com drives MG16D222 130R0290 MG16D222 Rev 2012 12 14...