Refer to 

VLT

®

 DriveMotor FCP 106 and FCM 106 Operating

Instructions

 for detailed information about safety precautions

for installation.

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. High voltage can be present even when the
warning LED indicator lights are off. Failure to wait the
specified time after power has been removed before
performing service or repair work can result in death or
serious injury.

1.

Stop the motor.

2.

Disconnect AC mains, permanent magnet type
motors, and remote DC-link supplies, including
battery back-ups, UPS, and DC-link connections to
other frequency converters.

3.

Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration
of waiting time is specified in 

Table 1.1

.

Voltage

[V]

Power Range

1)

[kW]

Minimum waiting

time

(min)

3x400

0.55–7.5

4

Table 1.1 Discharge Time

1) Power ratings relate to NO, see VLT

®

 DriveMotor FCP 106 and FCM 106

Operating Instructions.

Connection to FCP 106 or FCM 106

1.

Connect the LOP as shown in 

Table 1.2

 and

Illustration 1.3

.

2.

After completing connections, cut off or isolate
excess wire.

3.

Connect terminal 27 V to +24 V or set

parameter 5-12 Terminal 27 Digital Input

 to 

[0] No

operation

.

Terminal

Dual-speed

operation

Dual-mode

operation

Dual-direction

operation

18

Purple

Gray

19

27

Brown

29

Green

12

Red

50

Yellow

55

Blue

Table 1.2 Electrical Connections

Illustration 1.3 LOP Connections to FCP 106 or FCM 106

Installation Instructions

LOP Connection and Set-up
VLT

®

 DriveMotor FCP/FCM 106

2

Danfoss A/S © 09/2015 All rights reserved.

MI03L202