Drop cable
An alternative to splicing 2 trunk lines in the connector on
the control card is to use a DeviceNet connection box or a
T-connector. For this installation, a drop cable is available
as an option. Drop cable order number: 195N3113. The
connector is a micro-style, male, with rotating coupling
nut, and fits into a Micro Device port.
Illustration 3.10 Drop Cable
Wiring Procedure for Enclosure Types A4-A5, B1-B4, and
C1-C4
1.
Push the cable through cable glands.
2.
Mount the fieldbus connector on the fieldbus
option (terminal V-, CAN_L, Drain, CAN_H, V+).
3.
Prepare the fieldbus cable by stripping a section
of the cable insulation. Keep the unshielded wire
as short as possible. For cable specifications, refer
to
chapter 3.7.1 Cable Specifications
.
4.
Connect the fieldbus cable wires to the terminals
according to the colour code of the wires, see
Illustration 3.8
.
5.
Fix the cable screen to the metal base plate using
cable clamp or cable tie, see
Illustration 3.11
.
6.
Tighten cable glands securely.
130BD864.10
Illustration 3.11 Wiring for Enclosure Types A4-A5, B1-B4, and
C1-C4
Installation
VLT
®
DeviceNet MCA 104
10
Danfoss A/S © Rev. 03/2015 All rights reserved.
MG33D502
3
3