Decentral Solutions
Bit 09, Selection of ramp 1/2:
Bit 09 = "0" means that ramp 1 is active (parameters
207/208). Bit 09 = "1" means that ramp 2
(parameters 209/210) is active.
Bit 10, Data not valid/Data valid:
Is used to tell the variable frequency drive whether
the control word is to be used or ignored. Bit 10
=
’
0
’
causes the control word to be ignored, Bit
10 =
’
1
’
causes the control word to be used. This
function is relevant, because the control word is always
contained in the telegram, regardless of which type
of telegram is used, i.e. it is possible to turn off the
control word if you do not wish to use it in connection
with updating or reading parameters.
Bit 11, No function:
Bit 11 = digital output control.
Bit 12, No function:
Bit 12 = relay output control.
Bit 13/14, Selection of Setup:
Bits 13 and 14 are used to choose from the four menu
Setups according to the following table:
Setup
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
The function is only possible when
Multi-Setups
is
selected in parameter 004
Active Setup
.
Note: I parameter 507
Selection of Setup
a selection
is made to define how Bit 13/14 gates with the
corresponding function on the digital inputs.
Bit 15 Reverse
Bit 15 =
’
0
’
causes no reverse.
Bit 15 =
’
1
’
causes reverse.
Note: In the factory setting reverse is set to
digital
in parameter 506
Reverse
. Bit 15 only causes
reverse when either
Ser. communication
,
Logic
or
or
Logic and
is selected.
■
Status Word according to FC Profile
The status word is used to inform the master
(e.g. a PC) of the slave
’
s (variable frequency
drive) mode. Slave
Master.
Bit
Bit = 0
Bit =1
00
Control ready
01
Drive ready
02
Coasting stop
03
No trip
Trip
04
Not used
05
Not used
06
Trip lock
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local control
Ser. communi.
10
Outside
frequency range
Frequency limit
OK
11
Motor running
12
13
Voltage warn.
14
Current limit
15
Thermal warn.
Bit 00, Control ready:
Bit 00 =
’
1
’
. The variable frequency drive
is ready for operation.
Bit 00 =
’
0
’
. The variable frequency drive is
not ready for operation.
Bit 01, Drive ready:
Bit 01 =
’
1
’
. The variable frequency drive is ready for
operation, but there is an active coasting command
via the digital inputs or via serial communication.
Bit 02, Coasting stop:
Bit 02 =
’
0
’
. The variable frequency drive
has released the motor.
Bit 02 =
’
1
’
. The variable frequency drive can start
the motor when a start command is given.
Bit 03, No trip/trip:
Bit 03 =
’
0
’
means that the variable frequency
drive is not in fault mode.
MG.90.F2.22 - VLT is a registered Danfoss trademark
156
Содержание VLT Decentral FCD 300
Страница 28: ...Decentral Solutions Ordering form FCD 300 MG 90 F2 22 VLT is a registered Danfoss trademark 28 ...
Страница 48: ...Decentral Solutions Electrical Schematic MG 90 F2 22 VLT is a registered Danfoss trademark 48 ...
Страница 178: ...Decentral Solutions Dimensions of mounting brackets MG 90 F2 22 VLT is a registered Danfoss trademark 178 ...