Decentral Solutions
Programming, FCD
300
external references. If terminal 53 is applied to an analog
input voltage of 4 Volt the resulting reference will be:
Par. 214
Reference function
= Relative [1]:
Par. 204
Minimum reference
10.0 Hz
Reference effect at 4 Volt
16.0 Hz
Par. 215
Preset reference
2.4 Hz
Resulting reference
28.4 Hz
The graph shows the resulting reference in relation to
the external reference, which varies from 0-10 Volt.
Parameter 214
Reference function
is programmed
to
Sum
[0] and
Relative
[1] respectively. Also
shown is a graph in which parameter 215
Preset
reference 1
is programmed to 0 %.
214 Reference function
(REF FUNCTION)
Value:
✭
Sum (SUM)
[0]
Relative (RELATIVE)
[1]
External/preset (EXTERNAL/PRESET)
[2]
Function:
It is possible to define how preset references are to
be added to the other references; for this purpose,
use
Sum
or
Relative
. It is also possible by using the
External/preset
to select whether a shift between
external references and preset references is required.
External reference is the sum of the analog
references, pulse references and any references
from serial communication.
Description of choice:
If
Sum
[0] is selected, one of the adjusted
preset references (parameters 215-218
Preset
reference
) is summarized as a percentage of
the reference range (Ref
MIN
- Ref
MAX
), added to
the other external references.
If
Relative
[1] is selected, one of the added preset
references (parameters 215-218
Preset reference
)
is summarized as a percentage of the sum of
present external references.
If
External/preset
[2] is selected, it is possible via
a digital input to shift between external references
or preset references. Preset references will be a
percentage value of the reference range.
NOTE
If Sum or Relative is selected, one of the
preset references will always be active. If the
preset references are to be without influence,
they must be set to 0% (factory setting).
215 Preset reference 1 (PRESET REF. 1)
216 Preset reference 2 (PRESET REF. 2)
217 Preset reference 3 (PRESET REF. 3)
218 Preset reference 4 (PRESET REF. 4)
Value:
-100.00% - +100.00%
✭
0.00%
of the reference range/external reference
Function:
Four different preset references can be programmed
in parameters 215-218
Preset reference
.
The preset reference is stated as a percentage of the
reference range (Ref
MIN
- Ref
MAX
) or as a percentage
of the other external references, depending on the
choice made in parameter 214
Reference function
.
The choice between preset references can be made
via the digital inputs or via serial communication.
Preset ref., msb
Preset ref. lsb
0
0
Preset ref. 1
0
1
Preset ref. 2
1
0
Preset ref. 3
1
1
Preset ref. 4
Description of choice:
Set the preset reference(s) that is/are to be the options.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.90.F2.22 - VLT is a registered Danfoss trademark