6.4 Quick Transfer of Parameter Settings
between Multiple Frequency Converters
When the set-up of a frequency converter is completed, it
is recommended to store the data in the LCP or on a PC
via MCT 10 Set-up Software.
Data transfer from the frequency converter to the LCP:
1.
Go to
parameter 0-50 LCP Copy
.
2.
Press [OK].
3.
Select
[1] All to LCP
.
4.
Press [OK].
Connect the LCP to another frequency converter and copy
the parameter settings to this frequency converter as well.
Data transfer from the LCP to the frequency converter:
1.
Go to
parameter 0-50 LCP Copy
.
2.
Press [OK].
3.
Select
[2] All from LCP
.
4.
Press [OK].
6.5 Readout and Programming of Indexed
Parameters
Select the parameter, press [OK], and press [
▲
]/[
▼
] to scroll
through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the
value by pressing [
▲
]/[
▼
]. Press [OK] to accept the new
setting. Press [Cancel] to abort. Press [Back] to leave the
parameter.
6.6 Initialize the Frequency Converter to
Default Settings in two Ways
There are 2 ways to initialize the frequency converter to
the default settings.
Recommended initialization
1.
Select
parameter 14-22 Operation Mode
.
2.
Press [OK].
3.
Select
[2] Initialisation
and Press [OK].
4.
Power off the frequency converter and wait until
the display turns off.
5.
Reconnect the mains supply. The frequency
converter is now reset, except the following
parameters:
•
Parameter 1-06 Clockwise Direction
•
Parameter 8-30 Protocol
•
Parameter 8-31 Address
•
Parameter 8-32 Baud Rate
•
Parameter 8-33 Parity / Stop Bits
•
Parameter 8-35 Minimum Response Delay
•
Parameter 8-36 Maximum Response Delay
•
Parameter 8-37 Maximum Inter-char delay
•
Parameter 8-70 BACnet Device Instance
•
Parameter 8-72 MS/TP Max Masters
•
Parameter 8-73 MS/TP Max Info Frames
•
Parameter 8-74 "I am" Service
•
Parameter 8-75 Intialisation Password
•
Parameter 15-00 Operating hours
to
parameter 15-05 Over Volt's
•
Parameter 15-03 Power Up's
•
Parameter 15-04 Over Temp's
•
Parameter 15-05 Over Volt's
•
Parameter 15-30 Alarm Log: Error Code
•
15-4* Drive identification parameters
2-finger initialization
The other way to initialize the frequency converter to
default settings is through 2-finger initialization, which is
described in the following steps.
1.
Power off the frequency converter.
2.
Press [OK] and [Menu].
3.
Power up the frequency converter while still
pressing the keys for 10 s.
4.
The frequency converter is now reset, except the
following parameters:
•
Parameter 15-00 Operating hours
•
Parameter 15-03 Power Up's
•
Parameter 15-04 Over Temp's
•
Parameter 15-05 Over Volt's
•
15-4* Drive identification parameters
Initialization of parameters is confirmed by
alarm 80, Drive
initialised
in the display after the power cycle.
How to Program
VLT
®
Compressor Drive CDS 803
48