8.3.6 VLT
®
AutomationDrive FC 301, T2
Mains: 200-240 V, T2
FC 301
P
m
R
min
R
br,nom
Flat-pack IP65
R
rec
per item/P
br,cont.
Duty cycle
Danfoss part number
T2
[kW]
[
Ω
]
[
Ω
]
[
Ω
/W]
%
175Uxxxx
PK25
0.25
368
415.9
430/100
40
1002
PK37
0.37
248
280.7
330/100
27
1003
PK37
0.37
248
280.7
310/200
55
0984
PK55
0.55
166
188.7
220/100
20
1004
PK55
0.55
166
188.7
210/200
37
0987
PK75
0.75
121
138.4
150/100
14
1005
PK75
0.75
121
138.4
150/200
27
0989
P1K1
1.1
81.0
92.0
100/100
10
1006
P1K1
1.1
81.0
92.0
100/200
19
0991
P1K5
1.5
58.5
66.5
72/200
14
0992
P2K2
2.2
40.2
44.6
50/200
10
0993
P3K0
3
29.1
32.3
35/200
7
0994
P3K0
3
29.1
32.3
72/200
14
2x0992
P3K7
3.7
22.5
25.9
40/200
11
2x0996
Table 8.41 Mains: 200-240 V (T2)
8.3.7 VLT
®
AutomationDrive FC 302, T2
Mains: 200-240 V, T2
FC 302
P
m
R
min
R
br,nom
Flat-pack IP65
R
rec
per item/P
br,cont.
Duty cycle
Danfoss part number
T2
[kW]
[
Ω
]
[
Ω
]
[
Ω
/W]
%
175Uxxxx
PK25
0.25
380
475.3
430/100
40
1002
PK37
0.37
275
320.8
330/100
27
1003
PK37
0.37
275
320.8
310/200
54
0984
PK55
0.55
188
215.7
220/100
18
1004
PK55
0.55
188
215.7
210/200
36
0987
PK75
0.75
130
158.1
150/100
13
1005
PK75
0.75
130
158.1
150/200
27
0989
P1K1
1.1
81.0
105.1
100/100
9
1006
P1K1
1.1
81.0
105.1
100/200
18
0991
P1K5
1.5
58.5
76.0
72/200
13
0992
P2K2
2.2
45.0
51.0
50/200
9
0993
P3K0
3
31.5
37.0
35/200
7
0994
P3K0
3
31.5
37.0
72/200
14
2x0992
P3K7
3.7
22.5
29.7
40/200
10
2x0996
Table 8.42 Mains: 200-240 V (T2)
Selection Guide
Design Guide
64
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG90O202
8
8
Содержание VLT Brake Resistor MCE 101
Страница 2: ......