5-55 Term. 33 Low Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the low frequency
corresponding to the low motor
shaft speed (that is low reference
value) in
.
5-56 Term. 33 High Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the high frequency
corresponding to the high motor
shaft speed (that is high reference
value) in
parameter 5-58 Term. 33
High Ref./Feedb. Value
.
5-57 Term. 33 Low Ref./Feedb. Value
Range:
Function:
0 Referen-
ceFeedback
Unit
*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the low reference value [RPM]
for the motor shaft speed. This is
also the low feedback value, see
also
parameter 5-52 Term. 29 Low
Ref./Feedb. Value
.
5-58 Term. 33 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the high reference value
[RPM] for the motor shaft speed.
See also
parameter 5-53 Term. 29
High Ref./Feedb. Value
.
5-59 Pulse Filter Time Constant #33
Range:
Function:
100
ms
*
[5 - 1000
ms]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the pulse filter time constant. The
low-pass filter reduces the influence and
dampens oscillations on the feedback
signal from the control.
This is an advantage if there is a lot of
noise in the system.
NOTICE
These parameters cannot be adjusted while the motor is
running.
These parameters configure pulse outputs with their
functions and scaling. Terminals 27 and 29 are allocated to
pulse output via
parameter 5-01 Terminal 27 Mode
and
parameter 5-02 Terminal 29 Mode
, respectively.
Output value
Output
(Hz)
High output
value
P 5-60(term27)
P 5-63(term29)
High freq.
P 5-62(term27)
P 5-65(term29)
130BA089.11
Illustration 4.29 Configuration of Pulse Outputs
Options for readout output variables:
Parameters for configuring the scaling
and output functions of pulse
outputs. The pulse outputs are
designated to terminals 27 or 29.
Select terminal 27 output in
parameter 5-01 Terminal 27 Mode
and
terminal 29 output in
parameter 5-02 Terminal 29 Mode
.
[0]
No operation
[45]
Bus control
[48]
Bus control
timeout
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque relative to
limit
[105] Torque relative to
rated
[106] Power
[107] Speed
[108] Torque
[109] Max. out freq
[113] Ext. Closed Loop 1
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
No operation
Select the display output for
terminal 27.
[45]
Bus ctrl.
[48]
Bus ctrl.,
timeout
[100]
Output
frequency
[101]
Reference
[102]
Feedback
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
77
4
4