VLT
®
AutomationDrive FC 361
N200
N250
N315
High/normal overload
HO
NO
HO
NO
HO
NO
(High overload=150% current during 60 s, normal
overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
160
200
200
250
250
315
Typical shaft output at 460 V [hp]
250
300
300
350
350
450
Enclosure size
J9
Output current (3-phase)
Continuous (at 400 V) [A]
315
395
395
480
480
588
Intermittent (60 s overload) (at 400 V)[A]
473
435
593
528
720
647
Continuous (at 460 V) [A]
302
361
361
443
443
535
Intermittent (60 s overload) (at 460 V) [kVA]
453
397
542
487
665
589
Continuous kVA (at 400 V) [kVA]
218
274
274
333
333
407
Continuous kVA (at 460 V) [kVA]
241
288
288
353
353
426
Maximum input current
Continuous (at 400 V) [A]
304
381
381
463
463
567
Continuous (at 460 V) [A]
291
348
348
427
427
516
Maximum number and size of cables per phase
Mains, motor, brake, and load share [mm
2
(AWG)]
2x185 (2x350 mcm)
Maximum external mains fuses [A]
1)
550
630
800
Estimated power loss at 400 V [W]
2), 3)
3093
4116
4039
5137
5004
6674
Estimated power loss at 460 V [W]
2), 3)
2872
3569
3575
4566
4458
5714
Efficiency
3)
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
Weight, enclosure protection rating IP20 kg (lbs)
168.6 (371.6)
Efficiency
3)
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
Control card overtemperature trip [
°
C (
°
F)]
80 (176)
Table 10.2 Electrical Data for Enclosures J9, Mains Supply 3x380–480 V AC
1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
10.2 Mains Supply
Mains supply (L1, L2, L3)
Supply voltage
380–480 V ±10%
Mains voltage low/mains voltage drop-out:
During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop
level, which corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be
expected at mains voltage lower than 10% below the lowest rated supply voltage of the drive.
Supply frequency
50/60 Hz ±5%
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
1)
True power factor (λ)
≥0.9 nominal at rated load
Displacement power factor (cos Φ) near unity
(>0.98)
Specifications
VLT® AutomationDrive FC 361
58
Danfoss A/S © 06/2018 All rights reserved.
MG06I102