Switching on input supply L1, L2, L3 (power ups)
Maximum 1 time/2 minute
Environment according to EN60664-1
Overvoltage category III/pollution degree 2
The drive is suitable for use on a circuit capable of delivering up to 100 kA short circuit current rating (SCCR) at 480/600 V.
1) Calculations based on IEC61800-3.
10.3 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–590 Hz
1)
Output frequency in flux mode
0–300 Hz
Switching on output
Unlimited
Ramp times
0.01–3600 s
1) Dependent on voltage and power.
Torque characteristics
Starting torque (constant torque)
Maximum 150% for 60 s
1), 2)
Overload torque (constant torque)
Maximum 150% for 60 s
1), 2)
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
10.4 Ambient Conditions
Environment
J8/J9 enclosure
IP20/Chassis
Vibration test (standard/ruggedized)
0.7 g/1.0 g
Relative humidity
5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
Aggressive environment (IEC 60068-2-43) H
2
S test
Class Kd
Aggressive gases (IEC 60721-3-3)
Class 3C3
Test method according to IEC 60068-2-43
H2S (10 days)
Ambient temperature (at SFAVM switching mode)
- with derating
Maximum 55
°
C (131
°
F)
1)
- with full output power of typical EFF2 motors (up to 90% output current)
Maximum 50
°
C (122
°
F)
1)
- at full continuous FC output current
Maximum 45
°
C (113
°
F)
1)
Minimum ambient temperature during full-scale operation
0
°
C (32
°
F)
Minimum ambient temperature at reduced performance
-10
°
C (14
°
F)
Temperature during storage/transport
-25 to +65/70
°
C (13 to 149/158
°
F)
Maximum altitude above sea level without derating
1000 m (3281 ft)
Maximum altitude above sea level with derating
3000 m (9842 ft)
1) For more information on derating, see the design guide.
EMC standards, Emission
EN 61800-3
EMC standards, Immunity
EN 61800-3
Energy efficiency class
1)
IE2
1) Determined according to EN 50598-2 at:
•
Rated load.
•
90% rated frequency.
•
Switching frequency factory setting.
•
Switching pattern factory setting.
Specifications
Operating Guide
MG06I102
Danfoss A/S © 06/2018 All rights reserved.
59
10
10