Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
130BB934.11
Function
Setting
Parameter 5-10
Terminal 18
Digital Input
[8] Start
Parameter 5-11
Terminal 19
Digital Input
[10]
Reversing*
Parameter 5-12
Terminal 27
Digital Input
[0] No
operation
Parameter 5-14
Terminal 32
Digital Input
[16] Preset
ref bit 0
Parameter 5-15
Terminal 33
Digital Input
[17] Preset
ref bit 1
Parameter 3-10
Preset
Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
* = Default value
Notes/comments:
Table 8.7 Start/Stop with Reversing and 4 Preset Speeds
8.4 Wiring for External Alarm Reset
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
e30bg506.10
Function
Setting
Parameter 5-11 T
erminal 19
Digital Input
[1] Reset
* = Default value
Notes/comments:
Table 8.8 External Alarm Reset
8.5 Wiring for a Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
•
To meet PELV insulation requirements, use only
thermistors with reinforced or double
insulation.
Parameters
e30bg507.10
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
Function
Setting
Parameter 1-90
Motor Thermal
Protection
[2] Thermistor
trip
Parameter 1-93
Thermistor
Resource
[1] Analog
input 53
* = Default value
Notes/comments:
If only a warning is desired, set
parameter 1-90 Motor Thermal
Protection
to
[1] Thermistor
warning
.
Table 8.9 Motor Thermistor
Wiring Configuration Exampl...
VLT® AutomationDrive FC 361
42
Danfoss A/S © 06/2018 All rights reserved.
MG06I102
8
8