3.7 LCP Menus
3.7.1.1 Quick Menu Mode
The Quick Menu mode provides a list of menus used to
configure and operate the drive. Select the Quick Menu
mode by pressing the [Quick Menu] key. The resulting
readout appears on the LCP display.
e30bg568.10
Q1 My Personal Menu
Q2 Quick Setup
Q5 Changes Made
Q6 Loggings
0 RPM 0.00 A
Quick Menus
1(1)
Illustration 3.5 Quick Menu View
3.7.1.2 Q1 My Personal Menu
Use My Personal Menu to determine what is shown in the
display area. Refer to
chapter 3.6 Local Control Panel (LCP)
.
This menu can also show up to 50 pre-programmed
parameters. These 50 parameters are manually entered
using
parameter 0-25 My Personal Menu
.
3.7.1.3 Q2 Quick Setup
The parameters found in the
Q2 Quick Setup
contain basic
system and motor data that are always necessary for
configuring the drive. See
for the set-up procedures.
3.7.1.4 Q5 Changes Made
Select
Q5 Changes Made
for information about:
•
The 10 most recent changes.
•
Changes made from default setting.
3.7.1.5 Q6 Loggings
Use
Q6 Loggings
for fault finding. To get information about
the display line readout, select
Loggings
. The information is
shown as graphs. Only parameters selected in
parameter 0-20 Display Line 1.1 Small
through
parameter 0-24 Display Line 3 Large
can be viewed. It is
possible to store up to 120 samples in the memory for
later reference.
Q6 Loggings
Parameter 0-20 Display Line 1.1 Small
Speed [RPM]
Parameter 0-21 Display Line 1.2 Small
Motor Current
Parameter 0-22 Display Line 1.3 Small
Power [kW]
Parameter 0-23 Display Line 2 Large
Frequency
Parameter 0-24 Display Line 3 Large
Reference %
Table 3.7 Logging Parameter Examples
3.7.1.6 Main Menu Mode
The
Main Menu
mode lists all the parameter groups
available to the drive. Select the Main Menu mode by
pressing the [Main Menu] key. The resulting readout
appears on the LCP display.
e30bg272.10
O-** Operation / Display
1-** Load and Motor
2-** Brakes
3-** Reference / Ramps
0 RPM 0.00 A
Main Menu
1(1)
Illustration 3.6 Main Menu View
All parameters can be changed in the main menu. Option
cards added to the unit enable extra parameters associated
with the option device.
Product Overview
VLT® AutomationDrive FC 361
12
Danfoss A/S © 06/2018 All rights reserved.
MG06I102
3
3
Содержание VLT AutomationDrive FC 361
Страница 2: ......
Страница 81: ...Index Operating Guide MG06I102 Danfoss A S 06 2018 All rights reserved 79...