7.2.3 Entering System Information
NOTICE
SOFTWARE DOWNLOAD
For commissioning via PC, install MCT 10 Set-up
Software. The software is available for download (basic
version) or for ordering (advanced version, code number
130B1000). For more information and downloads, see
www.danfoss.com/en/service-and-support/downloads/dds/
vlt-motion-control-tool-mct-10/
The following steps are used to enter basic system
information into the drive. Recommended parameter
settings are intended for start-up and checkout purposes.
Application settings vary.
NOTICE
Although these steps assume that an asynchronous
motor is used, a permanent magnet motor can be used.
For more information on specific motor types, see the
product-specific
programming guide
.
1.
Press [Main Menu] on the LCP.
2.
Select
0-** Operation/Display
and press [OK].
3.
Select
0-0* Basic Settings
and press [OK].
4.
Press [Quick Menus] on the LCP and then select
02 Quick Setup
.
5.
Change the following parameters settings listed
in
if necessary. The motor data is found
on the motor nameplate.
Parameter
Default setting
Parameter 0-01 Language
English
Parameter 1-20 Motor Power [kW]
4.00 kW
Parameter 1-22 Motor Voltage
400 V
Parameter 1-23 Motor Frequency
50 Hz
Parameter 1-24 Motor Current
9.00 A
Parameter 1-25 Motor Nominal Speed
1420 RPM
Parameter 5-12 Terminal 27 Digital Input
Coast inverse
Parameter 3-02 Minimum Reference
0.000 RPM
Parameter 3-03 Maximum Reference
1500.000 RPM
Parameter 3-41 Ramp 1 Ramp up Time
3.00 s
Parameter 3-42 Ramp 1 Ramp Down Time
3.00 s
Parameter 3-13 Reference Site
Linked to Hand/
Auto
Parameter 1-29 Automatic Motor Adaptation
(AMA)
Off
Table 7.2 Quick Set-up Settings
NOTICE
MISSING INPUT SIGNAL
When the LCP shows AUTO REMOTE COASTING or
alarm
60, External Interlock
, the unit is ready to operate but is
missing an input signal. See
for details.
7.2.4 Configuring Automatic Energy
Optimization
Automatic energy optimization (AEO) is a procedure that
minimizes voltage to the motor, reducing energy
consumption, heat, and noise.
1.
Press [Main Menu].
2.
Select
1-** Load and Motor
and press [OK].
3.
Select
1-0* General Settings
and press [OK].
4.
Select
parameter 1-03 Torque Characteristics
and
press [OK].
5.
Select either
[2] Auto Energy Optim CT
or
[3] Auto
Energy Optim VT
and press [OK].
7.2.5 Configuring Automatic Motor
Adaptation
Automatic motor adaptation is a procedure that optimizes
compatibility between the drive and the motor.
The drive builds a mathematical model of the motor for
regulating output motor current. The procedure also tests
the input phase balance of electrical power. It compares
the motor characteristics with the data entered in
parameters 1-20
to
1-25
.
NOTICE
If warnings or alarms occur, see
. Some motors are unable to run the
complete version of the test. In that case, or if an output
filter is connected to the motor, select
[2] Enable reduced
AMA
.
Run this procedure on a cold motor for best results.
1.
Press [Main Menu].
2.
Select
1-** Load and Motor
and press [OK].
3.
Select
1-2* Motor Data
and press [OK].
4.
Select
parameter 1-29 Automatic Motor Adaptation
(AMA)
and press [OK].
5.
Select
[1] Enable complete AMA
and press [OK].
6.
Press [Hand On] and then [OK].
The test runs automatically and indicates when it
is complete.
Commissioning
Operating Guide
MG06I102
Danfoss A/S © 06/2018 All rights reserved.