5.9 Control Wiring
All terminals to the control cables are inside the drive
below the LCP. To access the control terminals, either open
the door (D1h/D2h/D5h/D6h/D7h/D8h) or remove the front
panel (D3h/D4h).
5.9.1 Control Cable Routing
•
Isolate control wiring from high-power
components in the drive.
•
Tie down all control wires after routing them.
•
Connect shields to ensure optimum electrical
immunity.
•
When the drive is connected to a thermistor,
ensure that the thermistor control wiring is
shielded and reinforced/double insulated. A 24 V
DC supply voltage is recommended.
Fieldbus connection
Connections are made to the relevant options on the
control card. For more detail, see the relevant fieldbus
instruction. The cable must be tied down and routed along
with other control wires inside the unit.
5.9.2 Control Terminal Types
shows the removable drive connectors.
Terminal functions and default settings are summarized in
–
.
130BF144.10
Illustration 5.35 Control Terminal Locations
12 13 18 19 27 29 32 33 20 37
39
69
68
61
42 50 53 54 55
130BF145.10
1
2
3
1
Serial communication terminals
2
Digital input/output terminals
3
Analog input/output terminals
Illustration 5.36 Terminal Numbers Located on the Connectors
Terminal
Parameter
Default
setting
Description
61
–
–
Integrated RC-filter for
cable shield. ONLY for
connecting the shield
to correct EMC
problems.
68 (+)
Parameter
group 8-3* FC
Port Settings
–
RS485 interface. A
switch (BUS TER.) is
provided on the
control card for bus
termination
resistance. See
.
69 (-)
Parameter
group 8-3* FC
Port Settings
–
Table 5.1 Serial Communication Terminal Descriptions
Digital input/output terminals
Terminal
Parameter
Default
setting
Description
12, 13
–
+24 V DC 24 V DC supply
voltage for digital
inputs and external
transducers.
Maximum output
current 200 mA for all
24 V loads.
18
Parameter 5-10
Terminal 18
Digital Input
[8] Start
Digital inputs.
19
Parameter 5-11
Terminal 19
Digital Input
[10]
Reversing
32
Parameter 5-14
Terminal 32
Digital Input
[0] No
operation
33
Parameter 5-15
Terminal 33
Digital Input
[0] No
operation
Electrical Installation
Operating Guide
MG34U502
Danfoss A/S © 09/2018 All rights reserved.
63
5
5