VLT
®
AutomationDrive FC 302
N160
N200
N250
High/normal overload
HO
NO
HO
NO
HO
NO
(High overload=150% current during 60 s.
Normal overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
160
200
200
250
250
315
Typical shaft output at 460 V [hp]
250
300
300
350
350
450
Typical shaft output at 500 V [kW]
200
250
250
315
315
355
Enclosure size
D2h/D4h/D7h/D8h
Output current (3-phase)
Continuous (at 400 V) [A]
315
395
395
480
480
588
Intermittent (60 s overload) (at 400 V)[A]
473
435
593
528
720
647
Continuous (at 460/500 V) [A]
302
361
361
443
443
535
Intermittent (60 s overload) (at 460/500 V) [kVA]
453
397
542
487
665
589
Continuous kVA (at 400 V) [kVA]
218
274
274
333
333
407
Continuous kVA (at 460 V) [kVA]
241
288
288
353
353
426
Continuous kVA (at 500 V) [kVA]
262
313
313
384
384
463
Maximum input current
Continuous (at 400 V) [A]
304
381
381
463
463
567
Continuous (at 460/500 V) [A]
291
348
348
427
427
516
Maximum number and size of cables per phase
- Mains, motor, brake, and load share [mm
2
(AWG)]
2x185 (2x400 mcm)
2x185 (2x400 mcm)
2x185 (2x400 mcm)
Maximum external mains fuses [A]
1)
550
630
800
Estimated power loss at 400 V [W]
2), 3)
3093
4116
4039
5137
5004
6674
Estimated power loss at 460 V [W]
2), 3)
2872
3569
3575
4566
4458
5714
Efficiency
3)
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [
°
C (
°
F)]
80 (176)
80 (176)
80 (176)
Table 10.4 Electrical Data for Enclosures D2h/D4h/D7h/D8h, Mains Supply 3x380–500 V AC
1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and
customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
Specifications
Operating Guide
MG34U502
Danfoss A/S © 09/2018 All rights reserved.
99