FC 300 Operating Instructions
How to Install
Load Sharing
With load sharing you can connect several FC 300’s DC intermediate circuits if you extend the installation
using extra fuses and AC coils (see illustration).
NB!:
Load sharing cables must be screened/armoured. If an unscreened/unarmoured cable is used,
some EMC requirements are not complied with. For more information, see
EMC specifications
in
the
VLT AutomationDrive FC 300 Design Guide
.
Voltage levels of up to 975 V DC may
occur between terminals 88 and 89.
No.
88
89
Loadsharing / DC link
DC -
DC +
Terminals
Brake Connection Option
The connection cable to the brake resistor must be
screened/armoured.
No. 81 82
Brake resistor
R-
R+ terminals
1.
Use cable clamps to connect the screen to the metal cabinet of the frequency converter and to the
decoupling plate of the brake resistor.
2.
Dimension the cross-section of the brake cable to match the brake current.
NB!:
Voltages up to 975 V DC may occur between the terminals.
NB!:
If a short circuit in the brake resistor occurs, prevent power dissipation in the brake resistor by
using a mains switch or contactor to disconnect the mains for the frequency converter. Only the
frequency converter can control the contactor.