2.8 Main Menu - Analog In/Out - Group 6
2.8.1 6-** Analog In/Out
Parameter group for configuration of the analog input and output.
2.8.2 6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
The frequency converter is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs can freely be allocated to either voltage (0 - 10 V) or
current input (0/4 - 20 mA)
NB!
Thermistors may be connected to either an analog or a digital input.
6-00 Live Zero Timeout Time
Range:
Function:
10 s*
[1 - 99 s]
Enter the Live Zero Time-out time period. Live Zero Time-out Time is active for analog inputs, i.e.
terminal 53 or terminal 54, used as reference or feedback sources. If the reference signal value
associated with the selected current input falls below 50% of the value set in par.6-10
, par.6-20
for a time period longer than the time set in par.6-00
, the function selected in par.6-01
will be activated.
6-01 Live Zero Timeout Function
Option:
Function:
Select the time-out function. The function set in par.6-01
will be acti-
vated if the input signal on terminal 53 or 54 is below 50% of the value in par.6-10
, par.6-20
for a time period defined in par.6-00
several time-outs occur simultaneously, the frequency converter prioritises the time-out functions
as follows:
1.
2.
The output frequency of the frequency converter can be:
•
[1] frozen at the present value
•
[2] overruled to stop
•
[3] overruled to jog speed
•
[4] overruled to max. speed
•
[5] overruled to stop with subsequent trip
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
86