6-02 Fire Mode Live Zero Timeout Function
Option:
Function:
The function set in par.6-01
will be activated if the input signal on
analogue inputs is below 50% of the value defined in parameter group 6-1* to 6-6* "Terminal xx
Low Current” or “Terminal xx Low Voltage" for a time period defined in par.6-00
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
2.8.3 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V*
[0.00 - par. 6-11 V]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par.6-14
Terminal 53 Low Ref./Feedb. Value
6-11 Terminal 53 High Voltage
Range:
Function:
10.00 V*
[par. 6-10 - 10.00 V]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par.6-15
Terminal 53 High Ref./Feedb. Value
6-12 Terminal 53 Low Current
Range:
Function:
4.00 mA*
[0.00 - par. 6-13 mA]
Enter the low current value. This reference signal should correspond to the low reference/feedback
value, set in par.6-14
Terminal 53 Low Ref./Feedb. Value
. The value must be set at >2 mA in order
to activate the Live Zero Time-out Function in par.6-01
6-13 Terminal 53 High Current
Range:
Function:
20.00 mA* [par. 6-12 - 20.00 mA]
Enter the high current value corresponding to the high reference/feedback set in par.6-15