6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the low voltage/low current set in par.
6-10
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
50.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
par.6-11
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 53. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
6-17 Terminal 53 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog
outputs are used as part of a decentral I/O system (e.g. when not part of any frequency converter
related control functions, but feeding an external control system with data)
[0]
Disabled
[1] *
Enabled
2.8.4 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V*
[0.00 - par. 6-21 V]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value, set in par.6-24
Terminal 54 Low Ref./Feedb. Value
6-21 Terminal 54 High Voltage
Range:
Function:
10.00 V*
[par. 6-20 - 10.00 V]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par.6-25
Terminal 54 High Ref./Feedb. Value
6-22 Terminal 54 Low Current
Range:
Function:
4.00 mA*
[0.00 - par. 6-23 mA]
Enter the low current value. This reference signal should correspond to the low reference/feedback
value, set in par.6-24
Terminal 54 Low Ref./Feedb. Value
. The value must be set at >2 mA in order
to activate the Live Zero Time-out Function in par.6-01
.
6-23 Terminal 54 High Current
Range:
Function:
20.00 mA* [par. 6-22 - 20.00 mA]
Enter the high current value corresponding to the high reference/feedback value set in par.
6-25
Terminal 54 High Ref./Feedb. Value
2 Parameter Description
VLT
®
AQUA Drive Programming Guide
88
MG.20.O4.02 - VLT
®
is a registered Danfoss trademark
2