The maximum rating of the over temperature contactor is 250V AC and 10A.
The switch must be used to prevent damage to the filter caused by over temperature.
4.1.7 Operation on Different Mains Type
Mains type
Operation of the filter module
TN/TT
Directly grounded star point
Allowed
TN
Indirectly grounded star point
Allowed
IT
Isolated net star/delta point
Allowed
Table 4.11: Different mains types
The filter has been designed completely symmetrically for three phase operation and without reference to the star point or protective earth.
4.1.8 Typical Installation in a Panel or Other Enclosures
To avoid high frequency noise coupling keep a minimum distance of 150 mm (5.91 inches) to:
a) mains/supply wires
b) motor wires of frequency converter
c) control- and signal wires (voltage range < 48 V)
To obtain low resistive HF-connections, grounding, screening and other metallic connections (e. g. mounting plates, mounted units) should have a surface
as large as possible to metallic ground. Use grounding and potential equalisation wires with a cross section as large as possible (min. 10mm²) or thick
grounding tapes.
Use copper or tinned copper screened wires only, as steel screened wires are not suitable for high frequency applications. Connect the screen with metal
clamps or metal glands to the equalisation bars or PE-connections.
Inductive switching units (relay, magnetic contactor etc.) must always be equipped with varistors, RC-circuits or suppressor diodes.