AHF 005/010
■
Power wiring size (copper)
Enclosure
Max. cable size mm
2
(AWG)
Type
A
16 (6)
Connector
B
16 (6)
Connector
C
50 (1/0)
Connector
D
50 (1/0)
Connector
E
*
Bus Bars
F
*
Bus Bars
G
*
Bus Bars
Overheat Contactor
4 (10)
Connector
*Power wiring used for connection of the filter AHF
005 and AHF 010 in enclosure size E, F and G must
be terminated with cable lugs that can be attached
to the input and output bus bars terminals. This
type of termination imposes no specifications of
the minimum and maximum cable size suitable for
connection. Power terminal details regarding the bus
bars can be found in the figures below.
Frame E
Frame F
Frame G
■
Operation on different mains type
Mains type
Operation of the filter module
TN
Directly grounded star point
Allowed
TN
Indirectly grounded star point
Allowed
IT
Isolated star point
Allowed
The filter module has been designed completely
symmetrically for three phase operation and without
reference to the star point or protective earth.
MG.80.B2.02 - VLT is a registered Danfoss trademark
12