AHF 005/010

Installation

NB!:

If several FC

s are to be connected to

the same filter, the harmonic filter must

be sized according to the sum of the

calculated input current to the FC

s.

Paralleling of filters

If the line input current of the frequency converter

exceeds the nominal current of the largest harmonic

filter, several harmonic filters can be paralleled to

achieve the necessary rating. Supply voltage must

be connected to the terminals X1.1, X1.2 and

X1.3 of the filters. The frequency converter supply

terminals L1, L2 and L3 must be connected to the

filter modules terminals X2.1, X2.2 and X2.3.

NB!:

Filters of different current ratings can be

paralleled. The rating of the filter becomes the

sum of the individual current ratings.

Use cables complying with local regulations.

Over temperature contactor

The Danfoss harmonic filter AHF 005 and AHF 010 is equipped with a galvanic isolated contactor that is
closed under normal operating conditions and open if the filter is overheated. This contactor can be used for
preventing damages to the filter caused by over temperature as shown in the following example.

Example: Connect terminal A of the harmonic filter to
terminal 12 or13 (voltage supply digital input, 24V)
of the Danfoss frequency converter and terminal
B to terminal 27 (digital input "Coast Inverse") the
frequency converter will let go of the motor (coasting)
and thereby unload the filter if a over temperature is
detected.

NB!:

The maximum rating of the over temperature

contactor is 250V AC and 10A.

MG.80.B2.02 - VLT is a registered Danfoss trademark

11

Содержание VLT AHF 005

Страница 1: ...Drives Solutions www danfoss com drives InstructionManual Harmonic Filter AHF 005 010...

Страница 2: ...ns weight 7 Dimension diagrams 8 Installation 10 Mechanical installation 10 Ventilation 10 Power wiring 10 Over temperature contactor 11 Power wiring size copper 12 Operation on different mains type 1...

Страница 3: ...rrectly and used in accordance with their purpose Avoid filter module damage 1 The filter modules are to be used only with Danfoss frequency converters The usage with other electrical loads is not per...

Страница 4: ...ortion to 10 AHF 005 reduces the total harmonic current distortion to 5 Current rating from 10A 324A For higher power modules can be paralleled One filter module can be used for several frequency conv...

Страница 5: ...8150 289 A 132 160 175G6610 175G6632 5200 5250 6175 6225 8200 8250 324 A 175G6611 175G6633 Higher ratings can be achieved by paralleling the filter units 360 A 200 Two 180 A units 5300 6275 8300 434...

Страница 6: ...rying from the input current ratings of VLT 5000 VLT 6000 and VLT 8000 series as stated in the respective operating instructions as these numbers are based on different operating conditions Calculatio...

Страница 7: ...al load If these conditions are not or only partially fulfilled a significant reduction of the harmonic components can still be achieved but the rated THiD values may not be achieved Environmental dat...

Страница 8: ...03 Kg 227 lbs 180 A E 107 Kg 236 lbs 217 A E 112 Kg 247 lbs 217 A E 119 Kg 262 lbs 289 A F 135 Kg 298 lbs 289 A F 145 Kg 320 lbs 324 A F 180 Kg 397 lbs AHF 005 380 415 V AC 50Hz AHF 005 440 480 V AC 6...

Страница 9: ...AHF 005 010 Dimension diagrams Frame size B Frame size C Frame size D MG 80 B2 02 VLT is a registered Danfoss trademark 8...

Страница 10: ...AHF 005 010 Specifications Frame size E Frame size F Frame size G MG 80 B2 02 VLT is a registered Danfoss trademark 9...

Страница 11: ...536 W 43 A 463 W 72 A 898 W 72 A 776 W 101 A 1260 W 101 A 1089 W 144 A 1796 W 144 A 1553 W 180 A 2245 W 180 A 1941 W 217 A 2706 W 217 A 2340 W 289 A 3604 W 289 A 3116 W 324 A 3493 W NB If other heat s...

Страница 12: ...lter becomes the sum of the individual current ratings Use cables complying with local regulations Over temperature contactor The Danfoss harmonic filter AHF 005 and AHF 010 is equipped with a galvani...

Страница 13: ...This type of termination imposes no specifications of the minimum and maximum cable size suitable for connection Power terminal details regarding the bus bars can be found in the figures below Frame...

Страница 14: ...m or thick grounding tapes Use copper or tinned copper screened wires only as steel screened wires are not suitable for high frequency applications Connect the screen with metal clamps or metal glands...

Страница 15: ...t correct a non intended operation of controller and or filter module is possible First powering up 1 Switch on mains supply The filter module is ready for operation at once 2 Check the readiness of t...

Страница 16: ...In particular during transport and handling no components are allowed to be bend and or isolating distances may not be altered The units are equipped with electrostatic sensitive devices which may be...

Страница 17: ...ecause of possibly charged capacitors During operation all covers and doors must be closed 7 Maintenance and service The manufacturer s documentation must be observed This safety information must be k...

Страница 18: ......

Отзывы: