MG.60.C4.02 – VLT is a registered Danfoss trademark
27
VLT
®
6000 HVAC
Freeze output request (FRZ.REQ.)
A freeze output command has been given,
but the motor will remain stopped until a
Run
permissive
signal is received via a digital input.
Reversing and start (START F/R)
Reversing and start
[2] on terminal 19
(parameter 303
Digital inputs
) and
Start
[1] on
terminal 18 (parameter 302
Digital inputs
) are
enabled at the same time. The motor will
remain stopped until one of the signals
becomes a logic ‘0’.
Automatic Motor Adaptation running
(AMA RUN)
Automatic motor adaptation has been
enabled in parameter 107
Automatic Motor
Adaptation, AMA
.
Automatic Motor Adaptation completed
(AMA STOP)
Automatic motor adaptation has ben
completed. The VLT frequency converter is
now ready for operation after the
Reset
signal
has been enabled. Please note that the motor
will start after the VLT frequency converter has
received the
Reset
signal.
Stand by (STANDBY)
The VLT frequency converter is able to start
the motor when a start command is received.
Stop (STOP)
The motor has been stopped via a stop signal
from a digital input, [OFF/STOP]-buttom or
serial communication.
DC stop (DC STOP)
The DC brake in parameter 114-116 has
been enabled.
DRIVE ready (UN. READY)
The VLT frequency converter is ready for
operation, but terminal 27 is a logic ‘0’ and/or
a
Coasting command
has been received via
the serial communi-cation.
Control ready (CTR.READY)
This status is only active when a profibus option
card is installed.
Not ready (NOT READY)
The VLT frequency converter is not ready for
operation, because of a trip or because OFF1,
OFF2 or OFF3 is a logic ‘0’.
Start disabled (START IN.)
This status will only be displayed if, in parameter
599
Statemachine
,
Profidrive
[1] has been
selected and OFF2 or OFF3 is a logic ‘0’.
Exceptions XXXX (EXCEPTIONS XXXX)
The microprocessor of the control card has
stopped and the VLT frequency converter is out
of operation.
The cause may be noise on the mains, motor or
control cables, leading to a stop of the control
card microprocessor.
Check for EMC-correct connection of these
cables.