VLT
®
6000 HVAC Series
Installation
■
Technical data, mains supply 3x380-460V
According to international requirements
VLT type
6016
6022
6027
6032
6042
Output current
I
VLT,N
[A] (380-440 V)
24.0
32.0
37.5
44.0
61.0
I
VLT, MAX
(60 s) [A]
(380-440 V)
26.4
35.2
41.3
48.4
67.1
I
VLT,N
[A] (441-460 V)
21.0
27.0
34.0
40.0
52.0
I
VLT, MAX
(60 s) [A]
(441-460 V)
23.1
29.7
37.4
44.0
57.2
Output power
S
VLT,N
[kVA] (400 V)
17.3
23.0
27.0
31.6
43.8
S
VLT,N
[kVA] (460 V)
16.7
21.5
27.1
31.9
41.4
Typical shaft output
P
VLT,N
[kW]
11
15
18.5
22
30
Typical shaft output
P
VLT,N
[HP]
15
20
25
30
40
Max. cable cross-section to
motor and DC-bus, IP 20
16/6
16/6
16/6
35/2
35/2
Max. cable cross-section to
motor and DC-bus, IP 54
[mm
2
]/[AWG]
2) 4)
16/6
16/6
16/6
16/6
35/2
Min. cable cross-section to
motor and DC-bus
[mm
2
]/[AWG]
2) 4)
10/8
10/8
10/8
10/8
10/8
Max. input current
I
L,N
[A] (380 V)
24.0
32.0
37.5
44.0
60.0
(RMS)
I
L,N
[A] (460 V)
21.0
27.6
34.0
41.0
53.0
Max. cable cross-section
power, IP 20
16/6
16/6
16/6
35/2
35/2
Max. cable cross-section
power, IP 54
[mm
2
]/[AWG]
2) 4)
16/6
16/6
16/6
16/6
35/2
Max. pre-fuses
[-]/UL
1)
[A]
63/40
63/40
63/50
63/60
80/80
Efficiency at rated frequency
0.96
0.96
0.96
0.96
0.96
Weight IP 20
[kg]
21
21
22
27
28
Weight IP 54
[kg]
41
41
42
42
54
Power loss at max. load.
[W]
419
559
655
768
1065
Enclosure
IP 20/ IP 54
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable
cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
MG.61.A5.02 - VLT is a registered Danfoss trademark
29