VLT
®
6000 HVAC Series
(VLT 6002 - 6072 380 - 460 V, 525-600 V and VLT 6002 - 6032 200 - 240 V).
If UL/cUL is to be complied with, copper cable with temperature class 75°C must be used
(VLT 6042 - 6062 200 - 240 V, VLT 6102 - 6602 380 - 460 V, VLT 6102 - 6652 525 - 600 V).
Connectors are for use of both copper and aluminium cables, unless other is specified.
Control characteristics:
Frequency range .................................................................................................................................. 0 - 1000 Hz
Resolution on output frequency ............................................................................................................. ±0.003 Hz
System response time ............................................................................................................................... 3 msec.
Speed, control range (open loop) ..................................................................................... 1:100 of synchro. speed
Speed, accuracy (open loop) ............................................................................ < 1500 rpm: max. error ± 7.5 rpm
>1500 rpm: max. error of 0.5% of actual speed
Process, accuracy (closed loop) ....................................................................... < 1500 rpm: max. error ± 1.5 rpm
>1500 rpm: max. error of 0.1% of actual speed
All control characteristics are based on a 4-pole asynchronous motor
Accuracy of display readout (parameters 009-012,
Display readout
):
Motor current [5] 0-140% load ............................................................... Max. error: ±2.0% of rated output current
Power kW [6], Power HP [7], 0-90% load .................................................. Max. error: ±5% of rated output power
Externals:
Enclosure ........................................................................................................... IP 00, IP 20, IP 21/NEMA 1, IP 54
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ............................................................ 93 % + 2 %, -3 % (IEC 68-2-3) for storage/transport
Max. relative humidity ............................................... 95 % non condensing (IEC 721-3-3; class 3K3) for operation
Aggressive environment (IEC 721-3-3) .................................................................................... Uncoated class 3C2
Aggressive environment (IEC 721-3-3) ........................................................................................ Coated class 3C3
Ambient temperature, VLT 6002-6005 200-240 V,
6002-6011 380-460 V, 6002-6011 525-600 V Bookstyle, IP 20 ............
Max. 45°C (24-hour average max. 40°C)
Ambient temperature, VLT 6006-6062 200-240 V,
6016-6602 380-460 V, 6016-6652 525-600 V IP 00, IP 20 ...................
Max. 40°C (24-hour average max. 35°C)
Ambient temperature, VLT 6002-6062 200-240 V,
6002-6602 380-460 V, VLT 6102-6652, 525-600 V, IP 54 .....................
Max. 40°C (24-hour average max. 35°C)
Min. ambient temperature in full operation ........................................................................................................ 0°C
Min. ambient temperature at reduced performance .....................................................................................
-10°C
Temperature during storage/transport ............................................................................................. -25 - +65/70°C
Max. altitude above sea level ...................................................................................................................... 1000 m
EMC standards applied, Emission ......................................... EN 61000-6-3/4, EN 61800-3, EN 55011, EN 55014
EMC standards applied, Immunity ................................................................................................ EN 50082-2, EN
61000-4-2, IEC 1000-4-3, EN 61000-4-4, EN 61000-4-5, ENV 50204, EN 61000-4-6, VDE 0160/1990.12
IP54 units are not intended for direct outdoor installation. The IP54 rating does not relate to other
exposures as sun, icing, wind blown driving rain. Under such circumstances Danfoss recommends to
install the units in an enclosure designed for these environmental conditions. Alternatively, an installation
at minimum 0.5 m above surface and covered by a shed is recommended.
MG.61.A5.02 - VLT is a registered Danfoss trademark
24