VLT
®
6000 HVAC Series
Programming
■
Inputs and outputs 300-365
In this parameter group, the functions that
relate to the input and output terminals of the
frequency converter are defined.
The digital inputs (terminals 16, 17, 18, 19, 27, 29,
32 and 33) are programmed in parameters 300-307.
The table below gives the options for programming the
inputs. The digital inputs require a signal of 0 or 24 V
DC. A signal lower than 5 V DC is a logic ‘0
’
, while
a signal higher than 10 V DC is a logic ‘1
’
.
The terminals for the digital inputs can be connected
to the internal 24 V DC supply, or an external 24
V DC supply can be connected.
The drawings in the next column show one Setup
using the internal 24 V DC supply and one Setup
using an external 24 V DC supply.
Switch 4, which is located
on the Dip switch control
card, is used for separating
the common potential of the
internal 24 V DC supply from
the common potential of the external 24 V DC
supply.
See
Electrical installation
.
Please note that when Switch 4 is in the OFF
position, the external 24 V DC supply is galvanically
isolated from the frequency converter.
Digital inputs
Terminal no.
16
17
18
19
27
29
32
33
parameter
300
301
302
303
304
305
306
307
Value:
No function
(NO OPERATION)
[0]
[0]
[0]
[0]
[0]
[0]
✭
[0]
✭
Reset
(RESET)
[1]
✭
[1]
[1]
[1]
[1]
Coasting stop, inverse
(COAST INVERSE)
[0]
✭
Reset and coasting stop,
inverse
(COAST & RESET INVERS)
[1]
Start
(START)
[1]
✭
Reversing
(REVERSE)
[1]
✭
Reversing and start
(START REVERSE)
[2]
DC-braking, inverse
(DC BRAKE INVERSE)
[3]
[2]
Safety Interlock
(SAFETY INTERLOCK)
[3]
Freeze Reference
(FREEZE REFERENCE)
[2]
[2]
✭
[2]
[2]
[2]
Freeze output
(FREEZE OUTPUT)
[3]
[3]
[3]
[3]
[3]
Selection of Setup, Isb
(SETUP SELECT LSB)
[4]
[4]
[4]
Selection of Setup, msb
(SETUP SELECT MSB)
[4]
[5]
[4]
Preset reference, on
(PRESET REF. ON)
[5]
[5]
[6]
[5]
[5]
Preset reference, lsb
(PRESET REF. SEL. LSB)
[6]
[7]
[6]
Preset reference, msb
(PRESET REF. MSB)
[6]
[8]
[6]
Speed down
(SPEED DOWN)
[7]
[9]
[7]
Speed up
(SPEED UP)
[7]
[10]
[7]
Run permissive
(RUN PERMISSIVE)
[8]
[8]
[11]
[8]
[8]
Jog
(JOG)
[9]
[9]
[12]
✭
[9]
[9]
Data change lock
(PROGRAMMING LOCK)
[10]
[10]
[13]
[10]
[10]
Pulse reference
(PULE REFERENCE)
[11]
[14]
Pulse feedback
(PULSE FEEDBACK)
[11]
Hand start
(HAND START)
[11]
[12]
[15]
[11]
[12]
Auto start
(AUTOSTART)
[12]
[13]
[16]
[12]
[13]
Fire mode
(FIRE MODE)
[13]
[14]
Fire mode inverse
(FIRE MODE INVERSE)
[14]
[15]
Enable RTC
(ENABLE RTC)
[25]
[25]
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.61.A5.02 - VLT is a registered Danfoss trademark