The VLT LonWorks option supports two
standard objects and three SNVTs, per the
LonMark standard object philosophy. The
standard objects are the 

Node Object

(containing the 

Object request, Object status,

and 

Object alarm) and the Controller object,

(containing the network variables described
in the preceding sections). The 

Object request

is a LonMark device used to obtain status and
alarm information from a node.

It is not necessary for a controller to support
the 

Node Object network variables. The

Object request, Object status and Object
alarm provide status and alarm information
for controllers that only support this type of
functionality. The status and alarm functions
described in the preceding sections contain
more drive specific information than 

Object

status and Object alarm.

1.  The VLT sends an 

Object status

containing drive status information
and an 

Object alarm containing fault

informationin response to the
following 

Object requests:

RQ_NORMAL,
RQ_UPDATE_STATUS, and
RQ_UPDATE_ALARM.

Network Variables for Node Object Support

Function

SNVT type

Variable Name

Input/Output

Object request

SNVT_obj_request

nviRequest

Input

Object status

SNVT_obj_status

nvoStatus

Output

Object alarm

SNVT_alarm

nvoAlarm

Output

A controller node error is written to VLT
parameter 201, 

Output Frequency Low Limit,

with 80.0 Hz when the high limit is 60 Hz

. The

conversion index is -1, with conversion factor 0.1.

The controller node sends the following
parameter write request to the VLT.

nvoParamCmd.learn =
LN_LEARN_CURRENT
nvoParamCmd.selector = 201
nvoParamCmd.value[0] = 0
nvoParamCmd.value[1] = 0
nvoParamCmd.value[2] = 3 hex
nvoParamCmd.value[3] = 20 hex (800
decimal)

The controller node receives the following
parameter access response from the VLT.

nviParamResp.learn = LN_NULL
nviParamResp.selector = 201
nviParamResp.value[0] = 0
nviParamResp.value[1] = 0
nviParamResp.value[2] = 0
nviParamResp.value[3] = 3 (illegal data
value)
nviParamResp.day = 0
nviParamResp.hour = 0
nviParamResp.minute = 0
nviParamResp.second = 0
nviParamResp.millisecond = 0

The nviRequest.object_id should be set
to “1” (controller node). The network
uses nviRequest, nvoStatus and
nvoAlarm variables for these functions.

2.  The VLT sends an 

Object status

containing a bit map of supported
status fields in response to all other
Object requests, including undefined
requests.

3.  The VLT 

Object status supports the

following status fields: invalid_id,
invalid_request,open_circuit,
out_of_service, electrical_fault,
comm_failure, manual_control, and
in_alarm. All other fields are always
set to “0.”

4.  The VLT sends an 

Object alarm

following any set or reset of a drive
fault condition.

5.  The 

Object alarm supports the

AL_ALM_CONDITION and
AL_NO_CONDITION alarm types.

Example 5:

Содержание VLT 6000 HVAC

Страница 1: ...VLT 5000 VLT 6000 HVAC VLT 8000 AQUA Rev 2004 03 11 www danfoss com drives 175R0948 MG60N202 MG60N202 Operating Instructions LonWorks FTP...

Страница 2: ...LonWorks FTP Option Card Instruction Manual...

Страница 3: ...done 2 The Stop Off key on the local control panel of the drive Touching electrical parts may be fatal even after equipment has been disconnected from AC line To be sure that capacitors have fully dis...

Страница 4: ...g Installation 10 Card Installation 10 Tools Required 10 VLT LonWorks Option Card 11 Installation Instructions 12 Network Initialization of LonWorks Option Card 19 Resource files 19 Free Topology Netw...

Страница 5: ...rks Network Configuration 25 Network Drive Control Input 26 Drive Feedback to Network 29 Drive Status Bit Definitions 31 Network Timer Functions 33 VLT Parameter Access 34 Parameter Access Error Codes...

Страница 6: ...tionandthe National Electrical Contractors Association of theUSA NECA Echelon LonTalk Neuron and LonWorks are registered trademarks of the Echelon Corporation VLT is a registered trademark of Danfoss...

Страница 7: ...nce is viewed in terms of transactions completed per second and response time Control systems do not need vast amounts of data but they do demand that the messages they send andreceiveareabsolutelycor...

Страница 8: ...service is acknowledged or end to end acknowledged service where a message is sent to a node or group of nodes and individual acknowledgments are ex pected from each receiver If an acknowledgment is n...

Страница 9: ...ssuming acknowledge or request response service For unacknowledged service an undetected collision means that the packet is not received and no retry is attempted knowledgments are generated by the ne...

Страница 10: ...nitially picks up the message It examines the source subnet field of the message and notes in its internal routing tables Learning Routers Source Echelon Corp that subnet 2 lies below it The router th...

Страница 11: ...ility of user or installer of VLT adjustable frequency drive to provide proper grounding and motor overload and branch protection according to National Electrical Code USA and local codes DANGER Wirin...

Страница 12: ...e Topology Model LEDs Terminal Connector Service Pin Switch SW1 Mounting Hole LEDs Terminal Connector Service Pin Switch SW3 Terminator Switch Ribbon Cable Socket to Memory Board Ribbon Cable Socket t...

Страница 13: ...oosen two captive screws C securing cassette to chassis 2 Disconnect Control Card Cassette IP20 NEMA 1 and Bookstyle Remove Local Control Panel LCP by pulling out from top of display A by hand LCP con...

Страница 14: ...same connec tions from which removed 4 Chassis Ground Connections Location of holes to mount grounding strips can vary with drive configuration When applicable remove mounting screws and washers loca...

Страница 15: ...rxT 20 screw driver 5 Install Chassis Ground Connections Ground Strips Attach ribbon cables between LonWorks control card and memory card Be sure exposed wire portion of ribbon cable A is facing front...

Страница 16: ...de of cassette and align screw holes 9 Insert LonWorks Card Route ribbon cables from LonWorks memory card through slot at side of control board cassette 8 Ribbon Cable Routing 7 Remove LCP Cradle IP20...

Страница 17: ...les Insert cables into corresponding sockets and fasten in accordance with directions in step 5 IP20 NEMA 1 and Bookstyle Insert cradle clips into holes in cassette Push down on cradle to snap it into...

Страница 18: ...into chassis 14 Install Ribbon Cables NOTE Ribbon cables must be recon nected to same connections from which removed IP20 NEMA 1 and IP54 NEMA 12 Springtensionclip A isusedasacable strain relief and...

Страница 19: ...nals C by firmly pressing them into connector receptacles A B C Connect signal wire NET A to terminal 79 and NET B to 80 of terminal connector In free topology model connections can be reversed IP20 N...

Страница 20: ...e drive without action beyond proper installation The card is then ready to be programmed for network operation The VLT LonWorks option supports three additional methods of addressing a node 1 Service...

Страница 21: ...these topologies The FTT transceiver located on the VLT LonWorks option card provides I O functions Flexible wiring capability simplifies system installation and makes it easy to add nodes for system...

Страница 22: ...tion is provided elsewhere in the network the termination function should be OFF Terminator switches position functions are provided in the table below Switch Position Functions Termination Pos 1 Pos...

Страница 23: ...owingspecificationsareforone network segment Multiple segments may be combined using repeaters to increase the number of nodes and distance Transmission Specifications Free Topology nodes run at 78 kb...

Страница 24: ...at a period greater than 2 seconds Flashing 5 times per second The response to the network management Wink command The VLT LonWorks node must be reset to leave the wink state OFF No power on board or...

Страница 25: ...hecksum Indicates watchdog timer resets occurring Possible corrupt EEPROM For Neuron 3150 chip based node use EEBLANK and follow reinitialization procedure Flashing at 1 second intervals Anytime Indic...

Страница 26: ...m 1 SNVT_rpm nciNmlSpeed 1 rpm 106 106 Min frequency1 SNVT_lev_percent nciMinSpeed 0 005 201 201 Max frequency1 SNVT_lev_percent nciMaxSpeed 0 005 202 202 Ramp up time 1 1 SNVT_time_sec NciRampUpTime...

Страница 27: ...e 1 Network variable nviRefPcnt is a signed value It represents the desired percentage of the VLT drive s reference range Range 163 840 163 835 All references provided to the drive are added to the to...

Страница 28: ...Setup 1 LSB Setup 2 MSB No function Jog 1 OFF Jog 2 OFF Data not valid No function 1 16 8 4 2 256 128 64 32 32768 Value 16384 8192 4096 2048 1024 512 No function Control Word Bit Descriptions for Coas...

Страница 29: ...OP Drive cannot run in AUTO mode but can run in HAND mode Parameter 504 DC Brake determines interaction with input 27 Drive Speed Setpoint With this input variable it is possible to give the Drive a S...

Страница 30: ...nt nvoOutputPcnt 0 005 163 835 163 840 Current1 SNVT_amp nvoDrvCurnt 0 1amps 3276 7 0 Energy SNVT_elec_kwh nvoDrvEnrg 1kWh 65 535 0 Power1 SNVT_power_kilo nvoDrvPwr 0 1kW 6553 5 0 Statusword SNVT_stat...

Страница 31: ...ine each bit Drive output 1 Network variable nvoOutputPcnt provides an analog indication of drive operation In open loop this is the drive output frequency in percentage within the reference range To...

Страница 32: ...1 16 normal Mtr Thermistor 12 8 no used 12 8 normal Motor thermal 13 4 normal Voltage Warn 13 4 normal Undervoltage 14 2 normal Current lim 14 2 normal Overvoltage 15 1 normal Therm Warning 15 1 norma...

Страница 33: ...Running 11 16 normal Over current 12 8 no used Stall Autostart 12 8 normal Torque limit 13 4 normal Voltage Warn 13 4 normal Motor Thermal 14 2 normal Current lim 14 2 normal Motor Overload 15 1 norm...

Страница 34: ...nd time This function sets the maximum time between transmissions for the network variables Drive Output 1 2 and 3 using the configuration network variable nciMaxSendT It can be used by the controller...

Страница 35: ...ce should compare the parameter number of the response message to the requested parameter number to determine that the information received is the requested information and not a response to another c...

Страница 36: ...and Response Examples Parameter 971 must be set to STORE ACTIVE SETUP for entering data values through LonWorks parameter access command in order to save changes in drive See parameter 971 in Paramet...

Страница 37: ...Cmd value 0 0 nvoParamCmd value 1 0 nvoParamCmd value 2 0 nvoParamCmd value 3 B4 hex 180 decimal The controller node receives the following parameter access response from the VLT nviParamResp learn LN...

Страница 38: ...ect alarm SNVT_alarm nvoAlarm Output A controller node error is written to VLT parameter 201 Output Frequency Low Limit with 80 0 Hz when the high limit is 60 Hz The conversionindexis 1 withconversion...

Страница 39: ...timeout 7 17 Standard bus timeout 8 16 Short circuit 9 15 Switch mode fault 10 14 Ground fault 11 13 Overcurrent 12 12 Torque limit 13 11 Motor thermistor 14 10 Motor overload 15 9 Inverter overload B...

Страница 40: ...addition to the parameters listed above the drive s control terminals issue digital inputs that control functions similar to those provided by nviStartStop nviResetFault and nviControlWord Parameters...

Страница 41: ...ocal control via the local control panel is enabled 3 Parameter 928 Access to process control is set to Disabled Normal control via the digital input terminals and the RS 485 interface is now enabled...

Страница 42: ...ter 804 is activated when bit 10 is 0 DataValue Disable DISABLE 0 Enable ENABLE 1 This parameter determines LonWorks control of the drive When Enable is selected drive parameters 503 through 508 deter...

Страница 43: ......

Страница 44: ...VLT 5000 VLT 6000 HVAC VLT 8000 AQUA Rev 2004 03 11 www danfoss com drives 175R0948 MG60N202 MG60N202 Operating Instructions LonWorks FTP...

Отзывы: