25
MG.60.N2.02 - VLT is a registered Danfoss trademark
VLT
®
5000 / VLT
®
6000 HVAC / VLT
®
8000 AQUA
The VLT LonWorks option card supports
LonMark network design to improve
interoperability. The Controller Object
contains the VLT Adjustable Frequency
Drive profile.
The configuration parameters are network
variable inputs to the VLT. Configuration of
parameters needs setting only one time,
usually at installation.
VLT 5000 parameters are shown in parenthesis, where applicable.
Configurations
properties
(Nci)
Function
SNVT type
Variable Name
Units
VLT 6000/8000
VLT 5000
parameter
parameter
Nom. motor freq.
1)
SNVT_freq_hz
nciNmlFreq
1 Hz
104
104
Nom. motor rpm
1)
SNVT_rpm
nciNmlSpeed
1 rpm
106
106
Min. frequency
1)
SNVT_lev_percent
nciMinSpeed
0.005%
201
201
Max. frequency
1)
SNVT_lev_percent
nciMaxSpeed
0.005%
202
202
Ramp up time 1
1)
SNVT_time_sec
NciRampUpTime
1 sec
206
207
Ramp down time 1
1)
SNVT_time_sec
NciRampDownTime
1 sec
207
208
Heart beat time
1)
SNVT_time_sec
NciSndHrtBt
0.1 sec
-
-
1)
Part of the LonMark Functional Profile for
Variable Speed Drive 6010 version 1.1
When the NciSndHrtBt time is active it will sent
the following variables:
• nvoDrvCurnt
• nvoDrvSpeed
• nvoDrvVolt
• nvoDrvPwr
Please note that nciNmlFreq and nciNmlSpeed
can only be written to when the VLT frequency
converter is stopped.
(EDIT SETUP SELECT)
NOTE
Please note that writing to Configuration
properties will be stored in the Non-Volatile
memory.
Continous writing to Configuration properties
may damage the Non-Volatile memory.