P2.2.10
(Local/Remote Control Application, Multi-Step Speed Control Application)
P2.2.22
(PID Control Application)
P2.2.3.3
(Multi-Purpose Control Application, Pump and Fan Control Application)
Use this parameter to select the range for the analog input signal.
10.84 (ID 326) AI2 Custom Setting Minimum
Location in the menu:
P2.2.11
(Local/Remote Control Application, Multi-Step Speed Control Application)
P2.2.23
(PID Control Application)
P2.2.3.4
(Multi-Purpose Control Application, Pump and Fan Control Application)
Use this parameter to adjust the minimum value of the analog input signal between -160%...160% freely.
See
10.80 (ID 322) AI1 Custom Setting Maximum
.
ID304
20 mA
0
ID303
ID327
f
out
AI2
(term. 3,4)
ID325 = 0
AI2 = 0-100%
ID326
ID325 = 1
AI2 = 20-100%
4 mA
ID325 = Custom
e
3
0
b
h
0
3
9
.1
0
Illustration 46: Analog input AI2 scaling
10.85 (ID 327) AI2 Custom Setting Maximum
Location in the menu:
P2.2.12
(Local/Remote Control Application, Multi-Step Speed Control Application)
P2.2.24
(PID Control Application)
P2.2.3.5
(Multi-Purpose Control Application, Pump and Fan Control Application)
Use this parameter to adjust the maximum value of the analog input signal between -160%...160% freely.
See
10.84 (ID 326) AI2 Custom Setting Minimum
.
10.86 (ID 328) AI2 Inversion
Location in the menu:
P2.2.13
(Local/Remote Control Application, Multi-Step Speed Control Application)
P2.2.25
(PID Control Application)
P2.2.3.6
(Multi-Purpose Control Application, Pump and Fan Control Application)
Use this parameter to invert the analog input signal.
See
10.81 (ID 323) AI1 Signal Inversion
In Local/Remote Control Application, AI2 is the place A frequency reference, when parameter
ID 117
= 1 (default).
10.87 (ID 329) AI2 Filter Time
Location in the menu:
AB296635287482en-000301 / DPD00903 | 197
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide