M4x16
(2.2 Nm)
e3
0b
h2
25
.1
0
7.
Put the cable entry plate with the cables into the groove on the frame of the drive.
e3
0b
h2
26
.1
0
8.
Connect the cables. See the correct tightening torques in
10.5 Tightening Torques of the Terminals
.
A
Expose the shield of all the 3 cables to make a 360-degree connection with the grounding clamps for cable shield.
B
Connect the phase conductors of the mains cable and of the motor cable, and the conductors of the brake resistor cable into
the correct terminals.
C
Attach the grounding conductor of each cable to a grounding terminal with a grounding clamp for grounding conductor.
D
Make sure that the external grounding conductor is connected to the grounding bar. See
Electrical Installation
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
46 | Danfoss A/S © 2019.05