10.6.9 Power Ratings of VACON® 100 HVAC, 208–240 V
Table 39: Power Ratings of VACON
®
100 HVAC, Mains Voltage 208–240 V, 50–60 Hz, 3~
Enclo-
sure
size
Drive type
(1)
Low Loadability:
Continuous current
I
L
[A]
(2)
Low Loadability:
Input current I
in
[A]
(2)
Low Loadabili-
ty: 10% over-
load current [A]
(2)
Motor shaft power
(3)
: 10% overload
40°C [kW]
Motor shaft
power
(3)
: 10%
overload 40°C
[hp]
MR4
0003
3.7
3.2
4.1
0.55
0.75
0004
4.8
4.2
5.3
0.75
1.0
0007
6.6
6.0
7.3
1.1
1.5
0008
8.0
7.2
8.8
1.5
2.0
0011
11.0
9.7
12.1
2.2
3.0
0012
12.5
10.9
13.8
3.0
4.0
MR5
0018
18.0
16.1
19.8
4.0
5.0
0024
24.2
21.7
26.4
5.5
7.5
0031
31.0
27.7
34.1
7.5
10.0
MR6
0048
48.0
43.8
52.8
11.0
15.0
0062
62.0
57.0
68.2
15.0
20.0
MR7
0075
75.0
69.0
82.5
18.5
25.0
0088
88.0
82.1
96.8
22.0
30.0
0105
105.0
99.0
115.5
30.0
40.0
MR8
0140
143.0
135.1
154.0
37.0
50.0
0170
170.0
162.0
187.0
45.0
60.0
0205
208.0
200.0
225.5
55.0
75.0
MR9A
0261
261.0
253.0
287.1
75.0
100.0
0310
310.0
301.0
341.0
90.0
125.0
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See
.
3
230 V
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 123