2
DKRCC.PI.AG0.A3.00 / 520H5200
© Danfoss A/S (AC-MCI sw) 2012-12
Example: TUA/TUAE
Example: TCAE
Range B
: -60 – -25 °C (-75 – -15 °F)
Range N:
-40 – +10 °C (-40 – +50 °F)
Orifice
no.
Rated capacity [kW]
Rated capacity [TR]
Code no.
R22
R134a R404A/
R507
R407C
R410A
R22
R134a R404A/
R507
R407C
R410A
TUA and TUAE
0
0.60
0.47
0.47
0.63
-
0.17
0.13
0.13
0.18
-
068U1030
1
0.90
0.70
0.70
0.92
1.3
0.25
0.19
0.19
0.26
0.40
068U1031
2
1.3
1.0
1.0
1.4
2.1
0.36
0.28
0.28
0.38
0.60
068U1032
3
1.8
1.4
1.4
1.9
2.9
0.50
0.39
0.39
0.53
0.80
068U1033
4
2.6
2.1
2.1
2.8
4.5
0.75
0.59
0.60
0.80
1.3
068U1034
5
3.5
2.7
2.8
3.8
5.9
1.00
0.78
0.79
1.1
1.7
068U1035
6
5.3
4.1
4.2
5.7
9.0
1.5
1.2
1.2
1.6
2.5
068U1036
7
7.0
5.5
5.6
7.5
12.0
2.0
1.6
1.6
2.1
3.4
068U1037
8
11.0
8.2
8.4
11.0
18.0
3.0
2.3
2.4
3.2
5.0
068U1038
9
16.0
12.0
12.0
17.0
26.0
4.5
3.5
3.5
4.8
7.5
068U1039
TCAE
1
17.5
12.0
13.5
19.0
23.0
5.0
3.5
3.8
5.4
6.5
068U4100
2
21.0
14.5
16.0
23.0
27.5
6.0
4.1
4.5
6.5
7.8
068U4101
3
26.5
18.0
20.0
28.5
34.0
7.5
5.2
5.7
8.1
9.8
068U4102
Orifice
no.
Rated capacity [kW]
Rated capacity [TR]
Code no.
R22
R404A/
R507
R407C
R22
R404A/
R507
R407C
TUA and TUAE
0
0.52
0.36
0.46
0.15
0.10
0.13
068U1030
1
0.68
0.50
0.58
0.19
0.14
0.16
068U1031
2
0.85
0.64
0.70
0.24
0.18
0.20
068U1032
3
1.2
0.89
1.0
0.34
0.25
0.28
068U1033
4
1.8
1.3
1.4
0.50
0.37
0.41
068U1034
5
2.3
1.8
1.9
0.66
0.50
0.55
068U1035
6
3.5
2.7
2.9
1.0
0.75
0.82
068U1036
7
4.7
3.5
3.9
1.3
1.0
1.1
068U1037
8
7.1
5.3
5.8
2.0
1.5
1.6
068U1038
9
10.4
7.8
8.5
2.9
2.2
2.4
068U1039
TCAE
1
12.5
10.9
10.3
3.6
2.7
3.1
068U4100
2
16.4
14.1
13.5
4.7
3.5
4.0
068U4101
3
21.6
19.4
18.0
6.1
4.6
5.5
068U4102