manualshive.com logo in svg
background image

2

Switch No. 1- 5/2 DAY or 7 DAY.

When the switch is in the 7 DAY position each day may be programmed

with different switching  times and temperatures. Placing the switch in

the 5/2 DAY position enables Monday to Friday to be programmed with

one  set  of  switching    times  and  temperatures,  and  Saturday  and

Sunday to be programmed with a different set.

Switch No. 2 - OSC ON or OSC OFF

This  is  used  to  enable  or  disable  the  optimum  start  control  (OSC)

function for event 1. To cater for different types of building construction

with differing fabric constants there are four start-up curves from which

to choose, (see the diagram over the page). These curves dictate how

long before event 1 the heating equipment will be switched on. The

selectable  start-up  durations  are  0:00,  0:30,  1:00,  1:30  or  2:00  (2

hours). (Selecting 0 effectively disables the function).
Once initiated the difference between the space temperature and the

event 1 temperature is used to generate a pre-heat period proportional

to the OSC period selected. The closer the space temperature is to the

event  1  temperature,  the  shorter  the  pre-heat  period.  Refer  to  the

earlier section on Optimum Start Control for more detail.
It is recommended that the initial setting of the OSC is 30 minutes. See

the section on post-commissioning.

Switch No. 3 - CHRONO or ON/OFF

With this switch set to ON/OFF the TP75 will act as a conventional room

thermostat, switching the heating plant to maintain the programmed

temperature. When set to CHRONO the control function selected by

switch No. 4 is enabled.

IMPORTANT

. For systems with motorised zone valves ON/OFF mode

is recommended.

Switch No. 4 - Chrono 6 or Chrono 3

This  switch  configures  the  TP75-RF  to  control  different  forms  of

heating system, typically as follows:
Use Chrono 3 for high thermal inertia systems, e.g. floor standing cast

iron boilers.
Use Chrono 6 for low thermal inertia systems, e.g. low water content

boilers and combi. boilers.
See the earlier section on Chrono-proportional Control for more detail.

5.

Position the slots in the top surface of the module over the lugs at the
top of the wallplate, and hinge downwards until the module is pressed
fully against the wallplate. Tighten the two screws from below to fix the
module to the wallplate.

6.

Before setting the programmes the unit and circuits should be checked.
Refer to the following Commissioning Instructions.

TP75-RF Installation

The TP75-RF is supplied with a wallplate for ease of mounting. The wallplate
is used solely for fixing the electronics module to the wall and contains no
terminals.

Fixing

Fig. 2 TP75-RF or TS2 location

1.

TP75-RF

     Select the desired fixing position. (This should adhere

to normal room thermostat practice, see Fig. 2).

Fig. 3

   Wallplate fixing clearances.

2.

When fixing the heating controller wallplate note that the terminals are
at the top and the vertical centre line of the heating controller is at the
right hand edge of the terminal 4 recess.  Observe the clearance
required for fitting and removal,  Fig. 3.

3.

Fix the wallplate to the wall.

4.

Before fixing the unit on to its wallplate, ensure that the four DIP
switches on the rear of the unit (see Fig. 4)  have been moved to the
required settings; the choices are:-

7 day

OSC OFF

ON/OFF

Chrono 3

5/2 day

OSC ON

CHRONO

Chrono 6

Fig. 4

Factory pre-set DIP switch settings.

A B C 1 2 3 4 5 6

30mm min

Clearance for

screwdriver access

Wall or plaster

box mounting

holes

Aperture for

rear entry

Terminals

Knockouts for bottom

cable entry

Outline of unit

Отзывы: