6

Commissioning (RF versions only)

To tune the RX receiver to the frequency of the thermostat 
signal, follow steps 1-5 below

LEARN

1. 

TP7000-RF

   Press the recessed 

RESET

 button, 

using a non-metallic object, to reset 
the unit. 

2. Press & hold the recessed 

LEARN

 button for 3 seconds, 

using a non-metallic object.

   NOTE: Thermostat now transmits continuously for 5 mins

3.

 RX1

   Press and hold buttons 

PROG and CH1

 

for 3 seconds until green light fl ashes once

4.

 RX2 (if applicable)

 Stat 1 - perform steps 1-3 
 Stat 2 - wait 5 mins, perform steps1-2 and then press  

 

PROG and CH2 on RX2

  
 RX3  (if applicable)

 

 Stat 1 - perform steps 1 – 3 
 Stat 2 - wait 5 mins, perform steps 1-2 and then press  

 

PROG and CH2 on RX3

 Stat 3 - wait 5 mins, perform steps 1-2 and then press  

 

PROG and CH3 on RX3

5. 

TP7000-RF

   Press 

 or 

 

to return the unit to  

 

 

normal operation.

RESET

GB - Installation Instructions

Receiver Wiring (RF models only) 

RX1 & 2  (3055 12/01)

COM

RX3 (3056 12/01)

RX1 & RX2

RX3

NB. For mains voltage operated systems link terminal 2 to mains live supply

Содержание TP7000M

Страница 1: ...sungen Inbetriebnahme Instruktion Instrucciones de instalaci n Instrucciones del usuario Instruktions vejledning Brugervejleding 7 day programmable room thermostat Installatie handleiding Instructiese...

Страница 2: ...Instrucciones de instalaci n 33 36 Instrucciones del usuario 37 42 Instruktions vejledning 43 46 Brugervejleding 47 52 Installatie handleiding 53 56 Instructiesevoor Gebruik 57 62 63 66 67 72 Instruk...

Страница 3: ...of output relay N A 1 x SPDT Type 1B Switch rating of relay contact voltage and current N A 3 1 A 230 volts Transmitter frequency RF only 433 92 MHz N A Transmitter range RF only 30 meters max N A Ra...

Страница 4: ...the back of the unit From the top left hand corner of the wallplate there must be clearances of at least 140mm to the right 15mm to the left 30mm above and 100mm below in order to mount the plug in m...

Страница 5: ...tain a set temperature achieving a constant ambient environment for the user L N M models only Setting Optimum Start Control 4 C 3 C 2 C 1 C A B C 120 min 90 min 60 min 30 min Event 1 time 0 D Set Sw2...

Страница 6: ...for 3 seconds until green light ashes once 4 RX2 if applicable Stat 1 perform steps 1 3 Stat 2 wait 5 mins perform steps1 2 and then press PROG and CH2 on RX2 RX3 if applicable Stat 1 perform steps 1...

Страница 7: ...s and temperatures which often suit most people If you want you can change any of these settings by following the instructions on pages 9 10 First follow the steps on page 8 to set your display prefer...

Страница 8: ...10 min increments This display will ONLY appear if the OSC function has been enabled by your installer Use the or buttons to select the OSC period The choices are 0 30 30 mins 1 00 1 hr 1 30 and 2 00...

Страница 9: ...NEXT to advance to next Event iv Repeat steps i ii iii above for Events 2 3 4 5 6 Programming in 7 day mode separate programmes for each day of the week 1 Before you change the preset programmes Your...

Страница 10: ...ntil colon ashes in display Press PROG until Event 1 ashes then press DAY until display shows Day 1 5 Follow steps b c on page 9 10 to programme times temperatures for weekdays Press DAY to programme...

Страница 11: ...ture if required When selected number of days have elapsed the unit will return to normal controlling according to your set programmes NOTE Press and buttons together to exit holiday mode if necessary...

Страница 12: ...a hours and press 4 times to remove override To alter main LCD display to show either time or actual room temperature press NEXT COPY together Batteries will last in excess of two years Low battery in...

Страница 13: ...Part No 37045 Issue 1 04 05 www danfoss com BusinessAreas Heating...

Отзывы: