Installation

Instructions

RA2000 One Pipe Steam (1PS)

Thermostatic Radiator Valve

VISXA222 © Danfoss 04/16

Installation:

1.

 With the heat source off, carefully remove

existing air vent from the radiator.

2.

 Carefully thread the valve body into the

radiator. Tighten the valve such that the

orientation of the air vent port is up.

The piping of an extension between the 

radiator and valve body should not be done.

    

               

             

   

3.

 Tighten the air vent (013L8011) to the valve 

body. 

If using an air vent not supplied by Danfoss, it 

must be a straight shank vent.

4.

 Mount the thermostatic operator to the 

valve. Refer to the installation instructions 

included with the thermostatic operator for 

proper mounting to the valve.

 

            

Valve Mounted Operator  

  

         

     

Wall Mounted Operator

Содержание RA2000

Страница 1: ...mostatic Radiator Valve Complete Assembly Thermostatic Operator 013G8250 shown Air Vent 013L8011 1PS Valve 013G0140 1 8 45 Street Elbows Optional 013L8300 Spare Parts Packing Gland 013G0290 Vacuum Breaker 013U7175 Free Standing Radiators Built In Sensor Use built in sensor when room air can pass freely over the sensor Free Standing Radiators Remote Sensor Use remote sensor when room air cannot pas...

Страница 2: ... the valve or vent Boiler Steam supply must be cycled by a reset control and must not run at constant pressure which would prevent air from entering back into the system Make sure that free standing radiators or cast iron convectors are properly pitched and that hand valves are FULLY open To aid in preventing overheating of rooms that are temperature satisfied boiler steam pressure must be kept lo...

Страница 3: ... such that the orientation of the air vent port is up The piping of an extension between the radiator and valve body should not be done 3 Tighten the air vent 013L8011 to the valve body If using an air vent not supplied by Danfoss it must be a straight shank vent 4 Mount the thermostatic operator to the valve Refer to the installation instructions included with the thermostatic operator for proper...

Страница 4: ...ation Move remote sensor or dial sensor to a different location The vacuum breaker mechanism may be clogged with debris Verify if excessive pressure is within system Under heating within room Ensure thermostatic operator is in an appropriate location Move remote sensor or dial sensor to a different location The air vent may be stuck closed Check riser air vent for main system Check the pitch of th...

Отзывы: