The CS500 can be mounted in one of three ways:
•
End (bulkhead) installation
•
Up to three units stacked on one another
•
Individually side mounted
Care must be taken to ensure that the device’s connector is positioned so that moisture drains away from
the connector.
If the device is side or stack mounted, provide a drip loop in the harness. If the device is mounted
vertically, the connector should be on the bottom of the module.
Provide strain relief for mating connector wires.
Antenna must be mounted on external surface with a view to the sky.
C
Caution
Device damage may occur. Use caution when installing CS500. Due to the size of the mating connector
wire bundle, it is possible to twist off the end cap of the module if excessive pressure is applied during
the installation of harness strain relief.
Fasteners
Recommended outer diameter (OD)
Recommended torque
6.0 mm [0.25 in]
2.26 N•m [20 in•lbs]
Antenna
Connector(s) and nuts
Recommended torque
Cellular & GNSS
0.5 N•m [4.5 in•lbs]
18mm nut
2.94 N•m [26 in•lbs]