Condensing unit controller
6.12 Controller settings
NOTE! In case of controller replacement beware that unit controller settings are different from default controller factory settings!
Function
Code
Min.value
Max.value
Default
controller
settings
Unit controller
settings
Normal operation
Set point Tc (regulation reference follows the number of degrees
above the outside temperature Tamb)
---
2.0 K
20.0 K
8.0 K
Regulation
Select SI or US display. 0=SI (bar and °C). 1=US (Psig and °F)
r05
0/ °C
1/F
0/ °C
Internal Main Switch. Manual and service = - 1, Stop regulation = 0,
Start regulation =1
r12
-1
1
0
1
Offset during night operation. During night operation the
reference is raised by this value
r13
0 K
10 K
2 K
Set point for suction pressure Ts
r23
-25 °C
10°C
-7°C
Readout of reference for Tc
r29
-
-
-
Min. condensing temperature (lowest permitted Tc reference)
r82
0°C
40°C
10°C
Max. condensing temperature (highest permitted Tc reference)
r83
0°C
50°C
40°C
Max. discharge gas temperature Td
r84
50°C
160°C
135°C
125°C
Alarms
Alarm time delay on signal on the DI2 input
A28
0 min.
240 min.
30 min.
Alarm for insufficient cooling in condenser. Set temperature
difference.
A70
3.0 K
20.0 K
10.0 K
Delay time for A70 alarm
A71
5 min.
240 min.
30 min.
Compressor
Min. ON-time
c01
5 s
240 s
5 s
Min. OFF-time
c02
3 s
240 s
30 s
Min. time between compressor starts
c07
0 min.
30 min.
5 min.
Pump down limit at which the compressor is stopped (setting 0.0
= function dis-activated)
C33
0.0 bar
15.0 bar
0.0 bar
2.3
Min. compressor speed
c46
30 rps
70 rps
30 rps
Start speed for compressor and min. speed for high condensing
temperatures
c47
30 rps
70 rps
50 rps
Max. compressor speed
c48
50 rps
100 rps
100 rps
Max. compressor speed during night operation (% value of c48)
c69
50%
100%
70%
Definition of compressor control:
0=no external start/stop;
1=switch on DI1 must start/stop;
2=inverter compressor speed control
c71
0
2
1
2
Time delay for high Td. The compressor will stop when time
expires
c72
0 min.
20 min.
3 min.
Max. pressure. Compressor stops if a higher pressure is recorded
c73
7.0 bar
50.0 bar
23.0 bar
25.8
Difference for max. pressure (c73)
c74
1.0 bar
10.0 bar
3.0 bar
Min. suction pressure Ps. Compressor stops if a lower pressure is
recorded
c75
-0.3 bar
10.0 bar
3.0 bar
2
Difference for min. suction pressure and pump down
c76
0.1 bar
5.0 bar
0.7 bar
Amplification factor Kp for compressors PI regulation
c82
3.0
30.0
20.0
Integration time Tn for compressors PI regulation
c83
30 s
360 s
60 s
Liquid Injection Offset
c88
0.1 K
20.0 K
5.0 K
Liquid Injection hysteresis
c89
10.0 K
30.0 K
15.0 K
Compressor stop delay after Liquid injection
c90
0 s
10 s
3 s
Desired compressor speed if the signal from the pressure
transmitter Ps fails
c93
30 rps
70 rps
60 rps
Min On time during Low Ambient LP
c94
0
0
120
Measured Tc for which the Comp min speed is raised to StartSpeed
c95
40.0
10.0
70.0
Control parameters
Amplification factor Kp for PI regulation
n04
1.0
20.0
7.0
Integration time Tn for PI regulation
n05
20
120
40
Kp max for PI regulation when the measurement is far from
reference
n95
5.0
50.0
20.0
33
FRCC.PC.044.A6.02
Application Guidelines