Instructions
52 | AN405821998738en-000102 - 118A5495A
© Danfoss | Climate Solutions | 2023.02 | LCA012A024
Rated Specifications
Item
Rating
Unit
Power source
3-phase, 380/400/415 V, 50 Hz
V
Power input
10.54/10.54/10.54
kW
Current
17.4/16.5/15.9
A
Conditions
1. Evaporating temperature: -10 °C
2. Ambient temperature: 32 °C
3. Suction superheat : 10K
Sound pressure level
The A-weighted sound pressure level does not exceed 70 dB(A).
(at a distance of 1 m from surface of product)
Performances (380 V / 400 V / 415 V)
Model : OP-UPAC015COP04E
Refrigerant fluid : R744
Ambient Temperature
Parameter
Symbol
Values
Unit
Evaporating temperature
t
e
-10
-35
°C
Application
MBP
LBP
Suction super heat
10
10
K
Sub cooling
0
0
K
Annual electricity consumption
Q
30535
43818
kWh/a
Seasonal Energy Performance Ratio
SEPR
3.95
1.74
32 °C
Rated cooling capacity
P
A
19.60
10.20
kW
Rated power input
D
A
10.54
10.39
kW
Rated COP
COP
A
1.86
0.98
25 °C
Rated cooling capacity
P
B
17.57
9.67
kW
Rated power input
D
B
6.92
7.65
kW
Rated COP
COP
B
2.54
1.26
15 °C
Rated cooling capacity
P
C
14.66
8.92
kW
Rated power input
D
C
4.01
5.37
kW
Rated COP
COP
C
3.65
1.66
5 °C
Rated cooling capacity
P
D
11.76
8.16
kW
Rated power input
D
D
2.09
3.90
kW
Rated COP
COP
D
5.63
2.09
43 °C
Rated cooling capacity
P
3
15.82
8.44
kW
Rated power input
D
3
10.99
10.68
kW
Rated COP
COP
3
1.44
0.79
Capacity control
Step / Variable
Degradation coefficient for fixed and staged units
0.25