3. Display item
Display of data and operation status
Order of display is “C00”
→
“C01” … “C93”
→
“C00”.
• Data
Table 1: Operation information
Code
No.
Display contents
Display
range
Min. unit
Setting for
combination
Remarks
Error
displa
[Exx]
Caution
display
[oPx][oPE-X]
Special
display
[QO][WLMC](ROM version display)
[oil]
Code
No.
Data display contents
Data
display
range
Min. unit
Remarks
<Sensor value, actuator information>
C00
CM1 operation frequency
0~255
1Hz
C02
Tho-A outdoor air temp.
L,-25~85
1°C
C03
Tho-G1 gas cooler inlet temp. 1
L,-30~150
1°C
C04
Tho-G2 gas cooler outlet temp. 2
L,-40~100
1°C
C05
Tho-M medium pressure receiver inlet temp.
L,-40~100
1°C
C06
Tho-INJ1 gas injection temp.
L,-40~100
1°C
C08
Tho-D1 discharge pipe temp. (CM1)
L,-30~150
1°C
C10
Tho-C under-dome temp. (CM1)
L,-30~150
1°C
C12
Tho-P1 power transistor temp. (CM1)
L,-20~120
1°C
C14
Tho-SC subcooling coil temp.
L,-40~100
1°C
C15
Tho-R liquid feed pipe temp.
L,-40~100
1°C
C16
Tho-S suction pipe temp.
L,-40~100
1°C
C18
CT1 (CM1) current
0~50
1A
C20
EEVG medium pressure receiver inlet electronic
expansion valve
0~470
1 pulse
C21
EEV-LB1 liquid bypass electronic expansion valve
0~470
1 pulse
C23
EEVSC subcooling coil expansion valve
0~470
1 pulse
C24
FM01 actual speed
0~999
(
*
1)
1
(10 min
-1
)
C25
FM02 actual speed
0~999
(
*
1)
1
(10 min
-1
)
C26
PSH high pressure sensor
0~15
0.01 Mpa
(0.1 Mpa
when 10.0 or
more)
C27
PSL low pressure sensor
0~8.5
0.01 Mpa
C28
PSM medium pressure sensor
0~8.5
0.01 Mpa
C29
Inverter 2ry current 1
0~50
1A
C31
Pressure switch
0, 1
(0: Open
1: Short)
100's place: 63H1, 2
10's place: Spare
1's place: Spare
C32
Level switch
0,1
100's place: OLS1-2 (*3)
10's place: Spare
1's place: Spare
C33
External input
0, 1
(0: Open
1: Short)
(*2)
100's place: CNS1
10's place: CNS2
1's place: CNS3
C35
Relay output
0, 1
(0: Open
1: Short)
100's place: 52X1
10's place: 52X2 (Spare)
1's place: (Spare)